Delta DVP-ES2 User Manual
Page 283
3 . I n s t r u c t i o n S e t
3 - 1 6 7
API Mnemonic
Operands
Function
65
STMR
Special Timer
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices
Word devices
Program Steps
Type
OP
X Y
M S K H KnX KnY KnM KnS T C D E F
S
*
m
*
*
D
*
*
*
STMR: 7 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: No. of timer (T0~T183) m: Set value in timer (m = 1~32,767, unit: 100ms)
D: Start No. of output devices (occupies 4 consecutive devices)
Explanations:
136. STMR instruction is specifically used for delay-OFF, ON/OFF triggered timer and flashing
circuit.
137. The timer number (S) specified by STMR instruction can be used only once
Program Example:
138. When X20 = ON, STMR sets T0 as the 5 sec special timer.
139. Y0 is the delay-OFF contact. When X20 is triggered, Y0 = ON; When X20 is OFF, Y0 = OFF
after a 5 sec delay.
140. When X20 goes from ON to OFF, Y1 = ON for 5 seconds.
141. When X20 goes from OFF to ON, Y2 = ON for 5 seconds.
142. When X20 goes from OFF to ON, Y3 = ON after a 5 second delay. When X20 turns from ON to
OFF, Y3 = OFF after a 5 second delay.
X20
STMR
T0
K50
Y0
X20
Y0
Y1
Y2
Y3
5 sec
5 sec
5 sec
5 sec
5 sec
5 sec