3 . I n s t r u c t i o n S e t
3 - 3 7 7
API Mnemonic
Operands
Function
160
TCMP P
Time compare
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices
Word devices
Program Steps
Type
OP
X Y
M S K H KnX KnY KnM KnS T C D E F
S
1
*
*
*
*
*
*
*
*
*
*
*
S
2
*
*
*
*
*
*
*
*
*
*
*
S
3
*
*
*
*
*
*
*
*
*
*
*
S
*
*
*
D
*
*
*
TCMP, TCMPP: 11 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S
1
: “Hour” for comparison (K0~K23) S
2
: “Minute” for comparison (K0~K59) S
3
: “Second” for
comparison (K0~K59) S: Current time of RTC (occupies 3 consecutive devices) D:
Comparison result (occupies 3 consecutive devices)
Explanations:
1.
TCMP instruction compares the time set in S
1
, S
2
, S
3
with RTC current value in S and stores
the comparison result in D.
2.
S: “Hour” of current time of RTC. Content: K0~K23. S +1: “Minute” of current time of RTC.
Content: K0~K59. S +2: “Second” of current time of RTC. Content: K0~K59.
3.
Usually the time of RTC in S is read by TRD instruction first then compared by TCMP
instruction. If operand S exceeds the available range, operation error occurs and M1067 = ON,
M1068 = ON. D1067 stores the error code 0E1A (HEX).
Program Example:
1.
When X0 = ON, the instruction executes and the RTC current time in D20~D22 is compared
with the set value 12:20:45. Comparison result is indicated by M10~M12. When X0 goes from
ON→OFF, the instruction is disabled however the ON/OFF status of M10~M12 remains.
2.
Connect M10 ~ M12 in series or in parallel to obtain the results of ≧, ≦, and ≠.
X0
M10
TCMP
K12
K20
K45
D20
M10
M11
M12
ON when 12:20:45
ON when 12:20:45
ON when 12:20:45
>
=
<