3 . I n s t r u c t i o n S e t

3 - 3 7 7

API Mnemonic

Operands

Function

160

TCMP P

Time compare

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y

M S K H KnX KnY KnM KnS T C D E F

S

1

*

*

*

*

*

*

*

*

*

*

*

S

2

*

*

*

*

*

*

*

*

*

*

*

S

3

*

*

*

*

*

*

*

*

*

*

*

S

*

*

*

D

*

*

*

TCMP, TCMPP: 11 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S

1

: “Hour” for comparison (K0~K23) S

2

: “Minute” for comparison (K0~K59) S

3

: “Second” for

comparison (K0~K59) S: Current time of RTC (occupies 3 consecutive devices) D:

Comparison result (occupies 3 consecutive devices)

Explanations:

1.

TCMP instruction compares the time set in S

1

, S

2

, S

3

with RTC current value in S and stores

the comparison result in D.

2.

S: “Hour” of current time of RTC. Content: K0~K23. S +1: “Minute” of current time of RTC.

Content: K0~K59. S +2: “Second” of current time of RTC. Content: K0~K59.

3.

Usually the time of RTC in S is read by TRD instruction first then compared by TCMP

instruction. If operand S exceeds the available range, operation error occurs and M1067 = ON,

M1068 = ON. D1067 stores the error code 0E1A (HEX).

Program Example:

1.

When X0 = ON, the instruction executes and the RTC current time in D20~D22 is compared

with the set value 12:20:45. Comparison result is indicated by M10~M12. When X0 goes from

ON→OFF, the instruction is disabled however the ON/OFF status of M10~M12 remains.

2.

Connect M10 ~ M12 in series or in parallel to obtain the results of ≧, ≦, and ≠.

X0

M10

TCMP

K12

K20

K45

D20

M10

M11

M12

ON when 12:20:45

ON when 12:20:45

ON when 12:20:45

>

=

<