beautypg.com

Data – Delta DVP-ES2 User Manual

Page 471

background image

3 . I n s t r u c t i o n S e t

3 - 3 5 5

Program Example 11: COM2 (RS-485), Function Code H10

1.

Function code K16 (H10): Write in multiple Word devices. Up to 16 Words can be written. For

PLC COM2 ASCII mode, only 8 words can be written.

2.

For ASCII or RTU mode, PLC COM2 stores the data to be sent in D1256~D1295, and the

received data in D1070~D1085.

3.

Take the connection between PLC COM2 and VFD-B AC motor drive for example, the tables

below explain the status when PLC COM2 writes multiple word devices in VFD-B.

H87

MOV

M1002

D1120

SET

M1120

K100

MOV

D1129

RST

M1127

Set communication protocol as 9600, 8, E, 1

Retain communication protocol

Set communication timeout as 100ms

MODRW

K16

K1

X0

H2000

D50

K2

Connection device
address: K1

Function code: K16
write in multiple Words

Data address: H2000

Data storing register

Data length(word)

Processing received data

ASCII mode: The received data is stored in D1070~D1085 in ASCII format

RTU mode: The received data is stored in D1070~D1085 in Hex

Reset M1127

M1127

SET

X0

M1122

Sending request

M1143 = OFF
ASCII mode

RST

M1143

M1143 = ON
RTU mode

SET

M1143

Receiving completed

ASCII mode (M1143 = OFF)

When X0 = ON, MODRW instruction executes the function specified by Function Code H10

PLC

ÖVFD-B, PLC transmits: “01 10 2000 0002 04 1770 0012 30”

VFD

ÖPLC, PLC receives: “01 10 2000 0002 CD”

Registers for

data

to be sent (sending messages)

Register

Data

Descriptions

D1256 Low byte

‘0’

30 H

ADR 1

D1256 High byte

‘1’

31 H

ADR 0

Address of VFD: ADR (1,0)

D1257 Low byte

‘1’

31 H

CMD 1

D1257 High byte

‘0’

30 H

CMD 0

Control parameter: CMD (1,0)

D1258 Low byte

‘2’

32 H

Data Address

This manual is related to the following products: