D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 1 5 8

Flag explanation:

M1040:

Disable step transition. When M1040 = ON, all motion of step points are disabled.

91. Manual operation mode: M1040 remains ON in manual mode.

92. Zero return mode/one cycle operation mode: M1040 remains ON in the interval after Auto

Stop and before Auto Start is pressed.

93. Step operation mode: M1040 remians ON until Auto Start is pressed.

94. Continuous operation mode: When PLC goes from STOP→RUN, M1040 = ON. When Auto

Start is pressed, M1040 turns OFF.

M1041:

Step transition starts. This special M indicates the transition from step point S2 to the next step

point.

95. Manual operation mode/Zero return mode: M1041 remians OFF.

96. Step operation mode/One cycle operation mode: M1041 = ON when Auto Start is pressed.

97. Continuous operation mode: M1041 stays ON when Auto Start is pressed and turns OFF

when Auto Stop is pressed.

M1042:

Enable pulse operation: When Auto Start is pressed, PLC sents out pulse once for operation. .

M1043:

Zero return completed: M1043 = ON indicates that zero return is completed.

M1044:

Zero point condition: In continuous operation mode, M1044 has to be ON as a condition for enabling

step transition from S2 to the next step point.

M1045:

Disable “all output reset” function.

y

If the machine (not at the zero point) goes,

-

from manual (S0) to zero return (S1)

-

from auto (S2) to manual (S0)

-

from auto (S2) to zero return (S1)

And

M1045 = OFF, any of the S among D

1

~ D

2

in action will be reset as well as the output Y.

M1045 = ON, output Y will be retained but the step in action will be reset.

y

If the machine (at the zero point) goes from zero return (S1) to manual (S0), no matter M1045

is ON or OFF, Y output will be retained but the step in action will be reset.