beautypg.com

8 m relay, M relay -17 – Delta DVP-ES2 User Manual

Page 49

background image

2 . P r o g r a m m i n g C o n c e p ts

Binary

Octal

Decimal (K)

BCD

Hexadecimal (H)

(BIN)

(OCT)

(DEC)

(Binary Code Decimal)

(HEX)

Costant K, No. of
registers M, S, T, C,
D, E, F, P, I devices

For PLC
internal
operation

For DIP Switch and 7-
segment display

No. of X, Y
relay

Constant H

1101 15

13

0011

D

1110 16

14

0100

E

1111 17

15

0101

F

10000 20

16

0110

10

10001 21

17

0111

11


2.8 M

Relay

The types and functions of special auxiliary relays (special M) are listed in the table below. Care

should be taken that some devices of the same No. may bear different meanings in different series

MPUs. Special M and special D marked with “*” will be further illustrated in 2.13. Columns marked

with “R” refers to “read only”, “R/W” refers to “read and write”, “-“ refers to the status remains

unchanged and “#” refers to that system will set it up according to the status of the PLC.

Special

M

Function

ES2
EX2

SS2 SA2 SX2

OFF

Ø

ON

STOP

Ø

RUN

RUN

Ø

STOP

Attrib.

Latch

Default

-ed

M1000*

OFF

ON

OFF R NO

OFF

Monitor normally open contact

M1001*

ON

OFF

ON R NO

ON

Monitor normally closed contact

Enable single positive pulse at the

moment when RUN is activate (Normally

OFF)

M1002*

OFF

ON

OFF R NO

OFF

Enable single negative pulse at the

moment when RUN is activate (Normally

ON)

M1003*

ON

OFF

ON R NO

ON

M1004* ON when syntax errors occur

OFF

OFF

- R

NO

OFF

M1008*

OFF

OFF

- R

NO

OFF

Watchdog timer (ON: PLC WDT time out)

Indicate LV signal due to 24VDC
insufficiency

M1009

OFF

- - R

NO

OFF

M1011* 10ms clock pulse, 5ms ON/5ms OFF

OFF

- - R

NO

OFF

100ms clock pulse, 50ms ON / 50ms
OFF

M1012*

OFF

- - R

NO

OFF

M1013* 1s clock pulse, 0.5s ON / 0.5s OFF

OFF

- - R

NO

OFF

M1014* 1 min clock pulse, 30s ON / 30s OFF

OFF

- - R

NO

OFF

M1015* Enable high-speed timer

OFF

- -

R/W

NO

OFF

M1016*

OFF

- -

R/W

NO

OFF

Indicate Year display mode of RTC.

M1017*

OFF

- -

R/W

NO

OFF

±30 seconds correction on real time clock

M1018

Flag for Radian/Degree, ON for degree

OFF

- -

R/W

NO

OFF

2 - 1 7

This manual is related to the following products: