beautypg.com

Delta DVP-ES2 User Manual

Page 325

background image

3 . I n s t r u c t i o n S e t

3 - 2 0 9

3.

The forward running function of Delta’s VFD series inverter can also be set by handy

instruction API 102 FWD instruction through COM2/COM3 on PLC.

Program Example 5: COM1 RS-232

1.

Only 8-bit mode is supported. Communication format and speed are specified by lower 8 bits

of D1036.

2.

STX/ETX setting function (M1126/M1130/D1124~D1126) is not supported.

3.

High byte of 16-bit data is not available. Only low byte is valid for data communication.

4.

Write the data to be transmitted in advance into registers starting from D100 and set M1312

(COM1 sending request) as ON

5.

When X10 = ON, RS instruction executes and PLC is ready for communication. D0 will then

start to send out 4 data continuously. When data sending is over, M1312 will be automatically

reset. (DO NOT apply RST M1312 in program). After approximate 1ms, PLC will start to

receive 7 data and store the data in 7 consecutive registers starting from D20.

6.

When data receiving is completed, M1314 will automatically be ON. When data processing on

the received data is completed, M1314 has to be reset (OFF) and the PLC will be ready for

communication again. However, DO NOT continuously execute RST M1314, i.e. it is

suggested to connect the RST M1314 instruction after the drive contact M1314

Receiving completed and flag reset

Setting communication protocol as 9600,8,E,1

Retain communication protocol

Set up communication time out as 100ms

M1002

MOV

H87

D1036

SET

M1138

MOV

K100

D1249

X0

RS

D100

K4

D120

K7

M1314

Processing received data

RST

M1314

Pulse for
sending request

Pulse

Write transmitting data in advance

Sending request

SET

M1312

Sending data: (PLC→External equipment)

D100L

D101L

D102L

D103L

Source data register, starting from
lower 8 bits of D100

Length = 4

This manual is related to the following products: