D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
3 - 3 5 2
Register
Data
Descriptions
D1260 下 ‘0’ 30
H
D1260 上 ‘0’ 30
H
D1261 下 ‘1’ 31H
D1261 上 ‘0’ 30
H
Number of Data (count by bit)
D1262 下 ‘0’ 30
H
D1262 上 ‘2’ 32
H
Byte Count
D1263 下 ‘3’ 33
H
D1263 上 ‘4’ 46
H
D1264 下 ‘1’ 33
H
D1264 上 ‘2’ 46
H
Data contents
1234H
Content of register D0
D1265 下
‘9’
39 H
LRC CHK 1
D1265 上
‘3’
33 H
LRC CHK 0
Checksum: LRC CHK (0,1)
Registers for received data (responding messages)
Register
Data
Descriptions
D1070 下
‘0’
30 H
ADR 1
D1070 上
‘1’
31 H
ADR 0
D1071 下
‘0’
31 H
CMD 1
D1071 上
‘F’
46 H
CMD 0
D1072 下 ‘0’
30
H
D1072 上 ‘5’
35
H
D1073 下 ‘0’
30
H
D1073 上 ‘0’
30
H
Data Address
D1074 下 ‘0’
30
H
D1074 上 ‘0’
30
H
D1075 下 ‘1’
31
H
D1075 上 ‘0’
30
H
Number of Data(count by bit)
D1076 下
‘D’
44 H
LRC CHK 1
D1076 上
‘B’
42 H
LRC CHK 0
RTU mode (M1143 = ON)
When X0 = ON, MODRW instruction executes the function specified by Function Code H0F
PLC1
Ö PLC2,PLC1 sends: “01 0F 0500 0010 02 34 12 21 ED”
PLC2
Ö PLC1,PLC1 receives: “01 0F 0500 0010 54 CB”