D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 3 7 8

API Mnemonic

Operands

Function

161

TZCP P

Time zone compare

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S

K H

KnX

KnY KnM KnS T C D E F

S

1

*

*

*

S

2

*

*

*

S

*

*

*

D

*

*

*

TZCP, TZCPP: 9 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S

1

: Lower bound of the time for comparison (occupies 3 consecutive devices) S

2

: Upper bound of

the time for comparison (occupies 3 consecutive devices) S: Current time of RTC (occupies 3

consecutive devices) D: Comparison result (occupies 3 consecutive devices)

Explanations:

1.

TZCP instruction compares current RTC time in S with the range set in S

1

~ S

2

and the

comparison result is stored in D.

2.

S

1

, S

1

+1, S

1

+2: The “hour”, “minute” and “second” of the lower bound value for comparison.

3.

S

2

, S

2

+1, S

2

+2: The “hour”, “minute” and “second” of the upper bound value for comparison.

4.

S, S +1, S +2: The “hour”, “minute” and “second” of the current time of RTC.

5.

Usually the time of RTC in S is read by TRD instruction first then compared by TZMP

instruction. If operand S, S

1

, S

2

exceed the available range, operation error occurs and M1067

= ON, M1068 = ON. D1067 stores the error code 0E1A (HEX).

6. If

S < S

1

and S < S

2

, D is ON. When S > S

1

and S > S

2

, D+2 is ON. For other conditions, D + 1

will be ON. (Lower bound S

1

should be less than upper bound S

2

.)

Program Example:

When X0 = ON, TZCP instruction executes and M10~M12 will be ON to indicate the comparison

results. When X0 = OFF, the instruction is disabled but the ON/OFF status of M10~M12 remains.

X0

M10

TZCP

D0

D20

D10

M10

M11

M12

ON when

ON when

ON when

D0 Hour

D1 Minute

D2 Second

D10 Hour

D11 Minute

D12 Second

D10 Hour

D11 Minute

D12 Second

D0 Hour

D1 Minute

D2 Second

D10 Hour

D11 Minute

D12 Second

D20 Hour

D21 Minute

D22 Second

D20 Hour

D21 Minute

D22 Second