beautypg.com

Delta DVP-ES2 User Manual

Page 186

background image

D V P - E S 2 / S A 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 7 0

API Mnemonic

Operands

Function

16

D FMOV P

Fill Move

Controllers

ES2/EX2 SS2

SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T C D E F

S

*

* *

*

*

*

*

*

*

*

*

D

*

*

*

*

*

*

n

*

*

FMOV, FMOVP: 7 steps

DFMOV, DFMOVP: 13

steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S: Source of data D: Destination of data n: Number of data to be moved

Explanations:

1.

The contents in n registers starting from the device designated by S will be moved to n

registers starting from the device designated by D. If n exceeds the actual number of

available source devices, only the devices that fall within the valid range will be used

2. If

operand

S use index register F, only 16-bit instruction is available

3.

The range of n: 1~ 512

Program example:

When X20 = ON, K10 will be moved to the 5 consecutive registers starting from D10

X20

D10

K5

FMOV

K10

K10

K10

K10

K10

K10

K10

D10

D11

D12

D13

D14

n=5