Delta DVP-ES2 User Manual
Page 186
D V P - E S 2 / S A 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
3 - 7 0
API Mnemonic
Operands
Function
16
D FMOV P
Fill Move
Controllers
ES2/EX2 SS2
SA2
SE
SX2
Bit Devices
Word devices
Program Steps
Type
OP
X Y M S K H
KnX
KnY KnM KnS T C D E F
S
*
* *
*
*
*
*
*
*
*
*
D
*
*
*
*
*
*
n
*
*
FMOV, FMOVP: 7 steps
DFMOV, DFMOVP: 13
steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: Source of data D: Destination of data n: Number of data to be moved
Explanations:
1.
The contents in n registers starting from the device designated by S will be moved to n
registers starting from the device designated by D. If n exceeds the actual number of
available source devices, only the devices that fall within the valid range will be used
2. If
operand
S use index register F, only 16-bit instruction is available
3.
The range of n: 1~ 512
Program example:
When X20 = ON, K10 will be moved to the 5 consecutive registers starting from D10
X20
D10
K5
FMOV
K10
K10
K10
K10
K10
K10
K10
D10
D11
D12
D13
D14
n=5