beautypg.com

Delta DVP-ES2 User Manual

Page 322

background image

D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3-206

Program Example 3: COM2 RS-485

1.

Connect PLC to VFD-B series AC motor drives (AC motor drive in ASCII Mode; PLC in 16-bit

mode and M1161 = OFF).

2.

Write the data to be sent into registers starting from D100 in advance in order to read 6 data

starting from address H2101 on VFD-B

MOV

D1120

H86

M1002

SET

M1120

SET

M1122

MOV

D1129

K100

X0

M1123

RST

M1123

RS

D100

K17

D120

K35

Processing received data

Set up communication protocol as
9600,7,E,1

Retain communication protocol

Set up communication time-out as 100ms

Write transmitting data in advance

Sending request

Reset M1123

Pulse for
sending request

Receiving
completed

PLC

Ö VFD-B, PLC sends “: 01 03 2101 0006 D4 CR LF “

VFD-B

Ö PLC, PLC receives “: 01 03 0C 0100 1766 0000 0000 0136 0000 3B CR LF “

Registers for sent data (PLC sends out messages)

Register

Data

Explanation

D100 low

‘: ’

3A H

STX

D100 high

‘0’

30 H

ADR 1

D101 low

‘1’

31 H

ADR 0

Address of AC motor drive: ADR (1,0)

D101 high

‘0’

30 H

CMD 1

D102 low

‘3’

33 H

CMD 0

Instruction code: CMD (1,0)

D102 high

‘2’

32 H

D103 low

‘1’

31 H

D103 high

‘0’

30 H

D104 low

‘1’

31 H

Start data address

D104 high

‘0’

30 H

D105 low

‘0’

30 H

D105 high

‘0’

30 H

D106 low

‘6’

36 H

Number of data (counted by words)

D106 high

‘D’

44 H

LRC CHK 1

D107 low

‘4’

34 H

LRC CHK 0

Error checksum: LRC CHK (0,1)

D107 high

CR

D H

D108 low

LF

A H

END