7 C AN o p e n F u n c t i o n a n d O p e r a t i o n

7 - 1 3

Initialization Pre-operational Operational

Stopped

EMCY X

X

Boot-up X

NMT

X

X

X

The format of the control message for the node state:

COB-ID

Byte 0

Byte 1

0 Command

specifier

(CS)

Slave address

(0: Broadcast)

The command specifiers are listed below.

Command specifier

(hex)

Function

01

Start the remote node

02

Stop the remote node

80

Enter the pre-operational state

81

Reset the application layer

82

Reset the communication

—

Error control services
The error control service is used to detect the disconnection of the node in the network. The
error control services can be classified into two types, i.e. Heartbeat and Node Guarding.
The PLC only supports Heartbeat. For example, the master can detect the disconnection of
the slave only after the slave enables the Heartbeat service.
The Heartbeat principle is illustrated as follows. The Hearbeat producer transmits the
Heartbeat message according to the Heartbeat producing time which is set. One or many
Heartbeat consumers detect the message transmitted by the Heartbeat producer. If the
consumer does not receive the message transmitted by the producer within the timeout
period, the CANopen communication is abnormal.

Reuqest

Receiving

Receiving


Request

Heartbeat consumer

Heartbeat producer

Heartbeat
producing
time

Heartbeat
timeout
period

Heartbeat evnet

Heartbeat
timeout
period

Receiving