D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 1 3 8

25. Four pulse output modes: (They are not applicable to DVP-SE.)

D1220

D1221

Mode

Output

K0

K1 K2

K3

K0

K1 K2

K3

#

Y0 Pulse Pulse A CW

Y1

Pulse

Dir

B

Pulse

Y2

Pulse

Pulse

A

CCW

Y3

Pulse

Dir

B

Pulse

Pulse: Pulse

A: A phase pulse

CW: clockwise

Dir: Direction

B: B phase pulse CCW:

Counter-clockwise

Note

#

: When D1220 is specified as K3, D1221 is invalid.

26. Four pulse output modes: (They are only applicable to DVP-SE.)

D1220

D1221

Mode

Output

K0 K1

K3

#

K0 K1 K3

#

Y0 Pulse Pulse

CW

Y1

Pulse

Dir

Pulse

Y2

Pulse

Pulse

CCW

Y3

Pulse

Dir

Pulse

27. Pulse output flags:

Output device

Y0

Y1

Y2

Y3

Completed Flag

M1029

M1030

M1102

M1103

Immediately pause

M1078

M1079

M1104

M1105

0.01~10Hz

output

M1190 M1191 M1192 M1193

a) M1029 = ON after Y0/Y1 (D1220=K1, pulse/Dir) output is completed.

M1102 = ON after Y2/Y3 (D1221=K1, pulse/Dir) output is completed.

M1029 = ON after the Y0/Y2 (D1220 = K3, CW/CCW) output is completed.

b) The execution completed flag M1029, M1030, M1102, and M1103 should be manually

reset by users after pulse output is completed.

c) When PLSY / DPLSY instruction is OFF, the pulse output completed flags will all be reset.

d) When M1190~M1192 = ON, the available output range for PLSY Y0~Y3 is 0.01~10Hz.

28. While the PLSY instruction is being executed, the output will not be affected if S

2

is changed.

To change the pulse output number, stop the PLSY instruction, then change the pulse number.

29. S

1

can be changed during program execution and the change will take effects until the

modified PLSY instruction is being executed.

30. The ratio of OFF time and ON time of the pulse output is 1:1.

31. If

operand

S

1

, S

2

use index F, only 16-bit instruction is available.