D V P - E S 2 / S X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l – P r o g r a m m i n g
3 - 4 8 2
API Mnemonic Operands
Function
274
D
BORI
Connect NC Contact in Parallel
by Specified Bit
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices
Word devices
Program Steps
Type
OP
X Y M S K H
KnX
KnY KnM KnS T C D E F
S
*
*
*
*
*
*
n
*
* *
*
*
*
*
*
*
*
*
BORI: 5 steps
DBORI: 9 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: Reference source device n: Reference bit
Explanations:
1.
For ES2/EX2 models, only V1.20 or above supports the function
2.
Available range for the value in operand n: K0~K15 for 16-bit instruction; K0~K31 for 32-bit
instruction.
3.
BORI instruction is used to connect NC contact in parallel, whose state is defined by the
reference bit n in reference device D, i.e. if the bit specified by n is ON, the NC contact will be
ON, and vice versa.
Program Example:
X0
Y1
BORI
D0
K0
Instruction:
Operation:
LD
X0
Load NO contact X0
BORI
D0 K0 Connect NC contact in
parallel, whose state is
defined by bit0 of D0
OUT
Y1