3 . I n s t r u c t i o n S e t
3 - 2 3
MOV K20E0 D10F0
E0 = 8 F0 = 14
20 + 8 = 28 10 + 14 = 24
Transmission K28 D24
The opposite diagram E, F index register modification
refers to the content in the operand changes with the
contents in E and F.
For example, E0 = 8 and K20E0 represents constant
K28 (20 + 8). When the condition is true, constant K28
will be transmitted to register D24.
Devices modifiable: P, X, Y, M, S, KnX, KnY, KnM, KnS, T, C, D.
E and F can modify the devices listed above but cannot modify themselves and Kn., e.g. K4M0E0
is valid and K0E0M0 is invalid. Grey columns in the table of operand at the beginning page of each
application instruction indicate the operands modifiable by E and F.
If you need to modify device P, I, X, Y, M, S, KnX, KnY, KnM, KnS, T, C and D by applying E, F, you
have to select a 16-bit register, i.e. you can designate E or F.