3 . I n s t r u c t i o n S e t

3 - 2 3

MOV K20E0 D10F0

E0 = 8 F0 = 14

20 + 8 = 28 10 + 14 = 24

Transmission K28 D24

The opposite diagram E, F index register modification

refers to the content in the operand changes with the

contents in E and F.

For example, E0 = 8 and K20E0 represents constant

K28 (20 + 8). When the condition is true, constant K28

will be transmitted to register D24.

Devices modifiable: P, X, Y, M, S, KnX, KnY, KnM, KnS, T, C, D.

E and F can modify the devices listed above but cannot modify themselves and Kn., e.g. K4M0E0

is valid and K0E0M0 is invalid. Grey columns in the table of operand at the beginning page of each

application instruction indicate the operands modifiable by E and F.

If you need to modify device P, I, X, Y, M, S, KnX, KnY, KnM, KnS, T, C and D by applying E, F, you

have to select a 16-bit register, i.e. you can designate E or F.