D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 3 5 8

2. M1136→M1138: retain communication setting

3. D1252→D1249: Set value for data receiving timeout

4. M1320→M1139: ASCII/RTU mode selection

5. M1316→M1312: sending request

6. M1318→M1314: receiving completed flag

H87

M OV

M1002

D1109

SET

M1136

K100

M OV

D1252

M ODRW

K16

K1

X0

H2000

D50

K2

Connection device address: K1

Function Code: K16
Write in multiple Word data

Data address: H2000

Datat register:
D50 = H1770, D51=H12

Data length: K2

SET

X0

M 1316

RST

M 1320

SET

M1320

M1320 = OFF

ASCII mode

Set communication protocol as 9600,8,E,1

Retain communication setting

Set communication t imeout as 100ms

Sending request

M1320 = ON
RTU mo de

RST

M1318

M1318

Reset M1318

ASCII mode: No processing on received data .

RTU m ode: No processing on received data .

Received data

Receiving completed

z

ASCII mode (COM3: M1320 = OFF, COM1: M1139 = OFF):

When X0 = ON, MODRW executes the function specified by Function Code H10

PLC

ÖVFD-B, PLC sends: “01 10 2000 0002 04 1770 0012 30”

VFD

ÖPLC, PLC receives: “01 10 2000 0002 CD”

(No processing on received data)

z

RTU Mode (COM3: M1320=On, COM1: M1139=On):

When X0 = ON, MODRW executes the function specified by Function Code H10

PLC

ÖVFD-B,PLC sends: “01 10 2000 0002 04 1770 0012 EE 0C”

VFD-B

ÖPLC, PLC receives :"01 10 2000 0002 4A08"

(No processing on received data)