D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

4.5.6 Command Code: 15, Force ON/OFF multiple contacts

Max contacts/coils available for Force ON/OFF: 255

Example: Set Coil Y007…Y000 = 1100 1101, Y011…Y010 = 01.

PC→PLC “: 01 0F 05 00 00 0A 02 CD 01 11 CR LF”

Sent message:

Field Name

ASCII

STX :

Slave Address

01

Command code

0F

Coil Address Hi

05

Coil Address Lo

00

Quantity of Coils Hi

00

Quantity of Coils Lo

0A

Byte Count

02

Force Data Hi

CD

Force Data Lo

01

Error Check (LRC)

11

END 1

0D (Hex)

END 0

0A (Hex)

PLC→PC “: 01 0F 05 00 00 0A E1 CR LF”

Feedback message:

Field Name

ASCII

STX :

Slave Address

01

Command code

0F

Register T0 Address Hi

05

Register T0 Address Lo

00

Preset Data Hi

00

Preset Data Lo

0A

Error Check (LRC)

E1

END 1

0D (Hex)

END 0

0A (Hex)

4.5.7 Command Code: 16, Set content of multiple registers

Example: Set register T0 to 00 0A , T1 to 01 02 .

PC→PLC “: 01 10 06 00 00 02 04 00 0A 01 02 D6 CR LF”