4.5.6 Command Code: 15, Force ON/OFF multiple contacts
Max contacts/coils available for Force ON/OFF: 255
Example: Set Coil Y007…Y000 = 1100 1101, Y011…Y010 = 01.
PC→PLC “: 01 0F 05 00 00 0A 02 CD 01 11 CR LF”
Sent message:
Field Name
ASCII
STX :
Slave Address
01
Command code
0F
Coil Address Hi
05
Coil Address Lo
00
Quantity of Coils Hi
00
Quantity of Coils Lo
0A
Byte Count
02
Force Data Hi
CD
Force Data Lo
01
Error Check (LRC)
11
END 1
0D (Hex)
END 0
0A (Hex)
PLC→PC “: 01 0F 05 00 00 0A E1 CR LF”
Feedback message:
Field Name
ASCII
STX :
Slave Address
01
Command code
0F
Register T0 Address Hi
05
Register T0 Address Lo
00
Preset Data Hi
00
Preset Data Lo
0A
Error Check (LRC)
E1
END 1
0D (Hex)
END 0
0A (Hex)
4.5.7 Command Code: 16, Set content of multiple registers
Example: Set register T0 to 00 0A , T1 to 01 02 .
PC→PLC “: 01 10 06 00 00 02 04 00 0A 01 02 D6 CR LF”