beautypg.com

1 basic instructions (without api numbers) – Delta DVP-ES2 User Manual

Page 118

background image

D V P - E S 2 / S A 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 2

3.1 Basic Instructions (without API numbers)

Execution speed

(us)

Instruction

Function

Operand

ES2/EX2/SS2

SA2/SX2

SE

Steps

LD

Load NO contact

X, Y, M, S, T, C

0.76

0.64

1~3

LDI

Load NC contact

X, Y, M, S, T, C

0.78

0.68

1~3

AND

Connect NO contact in series

X, Y, M, S, T, C

0.54

0.58

1~3

ANI

Connect NC contact in series

X, Y, M, S, T, C

0.56 0.62

1~3

OR

Connect NO contact in parallel

X, Y, M, S, T, C

0.54

0.62

1~3

ORI

Connect NC contact in parallel

X, Y, M, S, T, C

0.56

0.64

1~3

ANB

Connect a block in series

N/A

0.68

0.68

1

ORB

Connect a block in parallel

N/A

0.76 0.76

1

MPS

Start of branches. Stores current

result of program evaluation

N/A

0.74 0.68

1

MRD

Reads the stored current result

from previous MPS

N/A

0.64 0.54

1

MPP

End of branches. Pops (reads and

resets) the stored result in

previous MPS

N/A

0.64 0.54

1

OUT

Output coil

Y, S, M

0.88

0.68

1~3

SET

Latches the ON status

Y, S, M

0.76

0.68

1~3

RST

Resets contacts, registers or coils

Y, M, S, T, C, D,

E, F

2.2 1.04

3

MC

Master control Start

N0~N7

1

0.8

3

MCR

Master control Reset

N0~N7

1

0.8

3

END Program

End

N/A

1 0.8

1

NOP No

operation

N/A

0.4 0.5

1

P Pointer

P0~P255

0.4 0.5

1

I

Interrupt program pointer

I□□□

0.4 0.5

1

STL

Step ladder start instruction

S

2.2

2

1

RET

Step ladder return instruction

N/A

1.6

1.4

1

NP

Negative contact to Positive

contact

N/A 1.66

0.72

1

PN

Positive contact to Negative

contact

N/A 1.62

0.72

1

Note: The execution speed is obtained by basic test programs, therefore the actual instruction

This manual is related to the following products: