3 . I n s t r u c t i o n S e t

3 - 2 7 9

5.

If rising-edge (LDP, ANDP, ORP) or falling-edge (LDF, ANDF, ORF) contacts are used before

FWD, REV, STOP instructions, sending request flags M1122 (COM2) / M1316 (COM3) has to

be enabled in advance for obtaining correct operation.

6. For detailed information of associated flags and special registers, please refer to RS

instruction.

7.

M1177 = OFF, only Delta VFD-A is supported and the definition of each operand is:

a)

S

1

= Address of VFD-A. Range of S

1

: K0 ~ K31

b)

S

2

= Operation frequency of VFD. Set value for VFD A-type inverter: K0 ~ K4,000

(0.0Hz ~ 400.0Hz).

c)

n = Communication mode. Range: K1 ~ K2. n = 1: communicate with VFD at designated

address. n = 2: communicate with all connected VFDs. .

d)

The feedback data from the peripheral equipment will be stored in D1070 ~ D1080 After

data receiving is completed, PLC will check if all data are correct automatically. If there

is an error, M1142 will be ON. When n = 2, PLC will not receive any data.

Program Example: COM2 (RS-485)

1.

Communication between PLC and VFD-A series inverter. Retry for communication time-out

and data receiving error.

M1002

MOV

H0073

D1120

SET

M1120

MOV

K100

D1129

RST

M1127

M1127

X0

FWD

K0

K500

K1

SET

M1122

M1129

M1142

X0

Retry when receiving time-out occurs

Retry when data receiving error

Processing received data

Receiving completed

Communication instruction setting:
Device address: 0
Frequency: 500Hz
K1: communicate with the designated VFD

Set up communication protocol as
4800, 8, O, 1

Retain communication protocol

Set up communication time-out: 100ms

Sending request

Reset M1127

The received data is stored in low byte
of D1070 ~ D1080 in ASCII format.

PLC VFD-A, PLC sends: “C

0001 0500

VFD-A PLC, PLC receives: “C

0001 0500