D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

Communication Error Code

Function Group

M1025, D1025

Number

Contents:

In the connection between PLC and PC/HMI, M1025 will be ON when PLC receives illegal

communication request during the data transmission process. The error code will be stored in

D1025.

01: illegal instruction code

02: illegal device address.

03: requested data exceeds the range.

07: checksum error

Pulse output Mark and Mask function

Function Group

M1108, M1110, M1156, M1158, M1538, M1540, D1026, D1027, D1135, D1136,
D1232, D1233, D1234, D1235, D1348, D1349

Number

Contents:

Please refer to explanations of API 59 PLSR / API 158 DDRVI / API 197 DCLLM instructions.

Execution Completed Flag

Function Group

M1029, M1030, M1102, M1103

Number

Contents:

Execution Completed Flag:

MTR, HKY, DSW, SEGL, PR:

M1029 = ON for a scan cycle whenever the above instructions complete the execution.

PLSY, PLSR:

1.

M1029 = ON when Y0 pulse output completes.

2.

M1030 = ON when Y1 pulse output completes

3.

M1102 = ON when Y2 pulse output completes.

4.

M1103 = ON when Y3 pulse output completes.

5.

When PLSY, PLSR instruction are OFF, M1029, M1030, M1102, M1103 will be OFF as well.

When pulse output instructions executes again, M1029, M1030, M1102, M1103 will be OFF

and turn ON when execution completes.

6.

Users have to clear M1029 and M1030 manually.

INCD

:

M1029 will be “ON” for a scan period when the assigned groups of data comparison is completed

RAMP, SORT:

1.

M1029= ON when instruction is completed. M1029 must be cleared by user manually.

2.

If this instruction is OFF, M1029 will be OFF.