D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3-280

Registers for data to be sent (sending messages)

Register

Data

Descriptions

D1089 low

‘C’

43 H

Header of control string

D1090 low

♥’ 03

H

Checksum

D1091 low

☺’ 01

H

Command acknowledgement
(communication mode)

D1092 low

‘0’

30 H

D1093 low

‘0’

30 H

D1094 low

‘0’

30 H

D1095 low

‘1’

31 H

Communication address

D1096 low

‘0’

30 H

D1097 low

‘5’

35 H

D1098 low

‘0’

30 H

D1099 low

‘0’

30 H

Operation command

Registers for received data (responding messages)

Register

DATA

Explanation

D1070 low

‘C’

43 H

Header of control string

D1071 low

♥’ 03

H

Checksum

D1072 low

♠’ 06

H

Acknowledge back. (Check feedback data)
(correct: 06H, Error: 07 H)

D1073 low

‘0’

30 H

D1074 low

‘0’

30 H

D1075 low

‘0’

30 H

D1076 low

‘1’

31 H

Communication address

D1077 low

‘0’

30 H

D1078 low

‘5’

35 H

D1079 low

‘0’

30 H

D1080 low

‘0’

30 H

Operation command

2.

M1177 = ON, other Delta VFDs are supoported

a)

S

1

= Address of VFD-A. Range of S

1

: K0 ~ K255, when S

1

is specified as K0, PLC will

broadcast to all connected VFDs.

b)

S

2

= Running frequency of VFD. Please refer to manuals of specific VFD. In STOP

instruction, operand S

2

is reserved.

c)

n = Operation mode.

In FWD instruction: n = 0

Forward mode; n = 1

Forward JOG. Other values

will be regarded as normal forward mode.

In REV instruction: n = 0

Reverse mode; n = 1

Reverse JOG. Other values

will be regarded as normal reverse mode