3 . I n s t r u c t i o n S e t

3 - 2 8 1

In STOP instruction: operand n is reserved.

d)

When Forward JOG is selected in FWR instruction, set value in S

2

is invalid. If users

need to modify the JOG frequency, please refer to manuals of specific VFDs.

Program Example: COM2 (RS-485)

Communication between PLC and VFD-B series inverter (ASCII Mode, M1143 = OFF), Retry when

communication time-out occurs.

M1002

MOV

H86

D1120

SET

M1120

MOV

K100

D1129

RST

M1127

M1127

X0

FWD

K1

K500

K0

SET

M1122

M1129

X0

Retry when communication time-out occurs

Processing received data

Receiving completed

Communication instruction setting:
Device address: 1
Frequency: 500Hz
K0:normal forward

Set up communication protocol as
9600, 7, E, 1

Retain communication protocol

Set up communication time-out: 100ms

Sending request

Reset M1127

PLC VFD, PLC sends: “:01 10 2000 0002 04 0012 01F4 C2

VFD PLC, PLC sends: “:01 10 2000 0002 CD

Data to be sent (sending messages)

Data

Descriptions

‘0’

30 H

ADR 1

‘1’

31 H

ADR 0

Address of AC motor drive: ADR

(1,0)

‘1’

31 H

CMD 1

‘0’

30 H

CMD 0

Command code: CMD (1,0)

‘2’ 32

H

‘0’ 30

H

‘0’ 30

H

‘0’ 30

H

Data Address

‘0’ 30

H

‘0’ 30

H

‘0’ 30

H

‘2’ 32

H

Data content