3 . I n s t r u c t i o n S e t

3 - 3 3 7

PLC data receiving register:

Register

Data

Descriptions

D0 1234

H

PLC converts the data in address 0500H ~ 0515H and stores the
converted data automatically.

Analysis of the read status of PLC2 Y0~Y17: 1234H

Device

Status

Device

Status

Device

Status

Device

Status

Y0 OFF

Y1 OFF

Y2 ON Y3

OFF

Y4 ON Y5 ON Y6

OFF

Y7

OFF

Y10 OFF Y11 On Y12

OFF

Y13

OFF

Y14 ON Y15 OFF Y16

OFF

Y17

OFF

5.

Relative flags and data registers when COM1 / COM2 / COM3 works as Master:

COM2

COM1

COM3

Function

M1120 M1138

M1136

Retain communication setting

M1143 M1139

M1320

ASCII/RTU mode selection

D1120 D1036

D1109

Communication

protocol

COM.

setting

D1121

D1121

D1255

PLC communication address

M1122 M1312

M1316

Sending request

Sending

request

D1129

D1249

D1252

Set value for data receiving timeout (ms)

Receiving

completed

M1127 M1314

M1318

Data receiving completed

-

M1315

M1319

Data receiving error

- D1250

D1253

Communication

error

code

M1129 -

- Receiving

timeout

M1140

-

-

Data receiving error

M1141 -

-

Parameter error. Exception Code is stored in

D1130

Errors

D1130 -

-

Error code (Exception code) returning from

Modbus communication

Program Example 3: COM2 (RS-485), Function Code H03

1.

Function code K3 (H03): read multiple Word devices. Up to 16 words can be read. For COM2

ASCII mode, only 8 words can be read.

2.

For ASCII or RTU mode, PLC COM2 stores the data to be sent in D1256~D1295, converts the

received data in registers starting from S, and stores the converted 16-bit data in D1296 ~

D1311.