Delta DVP-ES2 User Manual
Page 453
3 . I n s t r u c t i o n S e t
3 - 3 3 7
PLC data receiving register:
Register
Data
Descriptions
D0 1234
H
PLC converts the data in address 0500H ~ 0515H and stores the
converted data automatically.
Analysis of the read status of PLC2 Y0~Y17: 1234H
Device
Status
Device
Status
Device
Status
Device
Status
Y0 OFF
Y1 OFF
Y2 ON Y3
OFF
Y4 ON Y5 ON Y6
OFF
Y7
OFF
Y10 OFF Y11 On Y12
OFF
Y13
OFF
Y14 ON Y15 OFF Y16
OFF
Y17
OFF
5.
Relative flags and data registers when COM1 / COM2 / COM3 works as Master:
COM2
COM1
COM3
Function
M1120 M1138
M1136
Retain communication setting
M1143 M1139
M1320
ASCII/RTU mode selection
D1120 D1036
D1109
Communication
protocol
COM.
setting
D1121
D1121
D1255
PLC communication address
M1122 M1312
M1316
Sending request
Sending
request
D1129
D1249
D1252
Set value for data receiving timeout (ms)
Receiving
completed
M1127 M1314
M1318
Data receiving completed
-
M1315
M1319
Data receiving error
- D1250
D1253
Communication
error
code
M1129 -
- Receiving
timeout
M1140
-
-
Data receiving error
M1141 -
-
Parameter error. Exception Code is stored in
D1130
Errors
D1130 -
-
Error code (Exception code) returning from
Modbus communication
Program Example 3: COM2 (RS-485), Function Code H03
1.
Function code K3 (H03): read multiple Word devices. Up to 16 words can be read. For COM2
ASCII mode, only 8 words can be read.
2.
For ASCII or RTU mode, PLC COM2 stores the data to be sent in D1256~D1295, converts the
received data in registers starting from S, and stores the converted 16-bit data in D1296 ~
D1311.