3-256

API Mnemonic Operands

Function

89

PLS

Rising-edge output

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T C D E F

S

*

*

PLS: 3 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S: Rising pulse output device

Explanations:

When X0 goes from OFF to ON (Rising-edge trigger), PLS instruction executes and S generates a

cycle pulse for one operation cycle.

Program Example:

Ladder Diagram:

X0

M0

PLS

M0

Y0

SET

Timing Diagram:

X0

M0

Y0

A scan cycle

Instruction

Code: Operation:

LD

X0

;

Load

NO

contact

of

X0

PLS

M0

; M0 rising-edge output

LD

M0

;

Load

NO

contact

of

M0

SET

Y0

;

Y0

latched

(ON)