beautypg.com

Delta DVP-ES2 User Manual

Page 307

background image

3 . I n s t r u c t i o n S e t

3 - 1 9 1

API Mnemonic

Operands

Function

74

SEGL

7-segment with Latch

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y

M S K H KnX KnY KnM KnS T C D E F

S

*

*

*

*

*

*

*

*

*

*

*

D

*

n

*

*

SEGL: 7 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S: Source device storing the value to be displayed in 7-segment display D: Output device for

7-segment display

n: Configuration setting of output signal (n = 0~7)

Explanations:

185. This instruction occupies 8 or 12 consecutive external output points starting from D for

displaying the data of 1 or 2 sets of 4-digit 7-segment display. Every digit of the 7-segment

display carries a “Drive” which converts the BCD codes into 7-segment display signal. The

drive also carries latch control signals to retain the display data of 7-segment display.

186. n specifies the number of sets of 7-segment display (1 set or 2 sets ), and designates the

positive / negative output of PLC and the 7-segment display.

187. When there is 1 set of 4-digit output, 8 output points will be occupied. When there are 2 sets

of 4-digit output, 12 output points will be occupied

188. When the instruction is executed, the output terminals will be scanned circularly. When the

drive contact goes from OFF to ON again during the execution of instruction, the scan will

restart from the beginning of the output terminals.

189. Flag: When SEGL is completed, M1029 = ON for one scan cycle.

190. There is no limitation on the times of using this instruction in the program, however only one

instruction is allowed to be executed at a time.

Program Example:

191. When X20 = ON, SEGL instruction executes and Y24~Y27 forms an output scan loop for

7-segment display. The value of D10 will be mapped to Y20~Y23, converted to BCD code

and sent to the 1st set of 7-segment display. The value of D11 will be mapped to Y30~Y33,

converted to BCD code and sent to the 2

nd

set of 7-segment display. If the values in D10 and

D11 exceed 9,999, operational error will occur.

X20

SEGL

D10

Y20

K4