3 . I n s t r u c t i o n S e t
3 - 1 8 1
API Mnemonic
Operands
Function
69
D SORT
Data sort
Controllers
ES2/EX2 SS2 SA2
SE
SX2
Bit Devices
Word devices
Program Steps
Type
OP
X Y
M S K H KnX KnY KnM KnS T C D E F
S
*
m
1
* *
m
2
* *
D
*
n
*
*
*
SORT: 11 steps
DSORT: 21 steps
PULSE 16-bit 32-bit
ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2 ES2/EX2 SS2
SA2
SE
SX2
Operands:
S: Start device for the source data m
1
: Groups of data to be sorted (m
1
=1~32) m
2
: Number of
columns in the table (m
2
=1~6) D: Start device for the sorted data n: The No. of column to be
sorted. (n=1~ m2)
Explanations:
154. The sorted data is stored in the m
1
× m
2
registers starting from the device designated in D.
Therefore, if S and D designate the same register, the sorted results will be the same.
155. SORT instruction is completed after m
1
times of scan. Once the SORT instruction is completed,
the Flag M1029 (Execution completed flag) = ON.
156. There is no limitation on the times of using this instruction in the program. However, only one
instruction can be executed at a time
Program Example:
When X0 = ON, the sorting process starts. When the sorting is completed, M1029 will be ON. DO
NOT change the data to be sorted during the execution of the instruction. If the sorting needs to be
executed again, turn X0 from OFF to ON again.
X0
SORT
D0
K5
K5
D50
D100