D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3-242

Device

No.

Function

Setup Range

Explanation

2: Reverse control (E = PV - SV).

3: Auto-tuning of parameter exclusively for the temperature

control. The device will automatically become K4 when

the auto-tuning is completed and K

P

, K

I

and K

D

is set with

appropriate value (not avaliable in the 32-bit instruction).

4: Exclusively for the adjusted temperature control (not

avaliable in the 32-bit instruction).

5: Automatic mode with MV upper/lower bound control.

When MV reaches upper/lower bound, the accumulation

of integral value stops.

10: T

I

/ T

D

mode with MV upper/lower bound control. When

MV reaches upper/lower bound, the accumulation of

integral value stops.

S

3

+5:

Tolerable range for

error (E)

0~32,767

E = the error between SV and PV. If S

3

+5 is set as 5, when E is between -5

and 5, E will be 0. When S

3

+5 = K0,

the function will not be enabled.

S

3

+6:

Upper bound of

output value (MV)

-32,768~32,767

Ex: if S

3

+6 is set as 1,000, MV will be

1,000 when it exceeds 1,000. S

3

+6 has

to be bigger or equal to

S

3

+7, otherwise the upper bound and

lower bound value will switch.

S

3

+7:

Lower bound of

output value (MV)

-32,768~32,767

Ex: if S

3

+7 is set as -1,000, MV will be

-1,000 when it is smaller than -1,000..

S

3

+8:

Upper bound of

integral value

-32,768~32,767

Ex: if S

3

+8 is set as 1,000, the integral

value will be 1,000 when it is bigger

than 1,000 and the integration will

stop. S

3

+8 has to be bigger or equal S

3

+9; otherwise the upper bound and

lower bound value will switch

S

3

+9:

Lower bound of

integral value

-32,768~32,767

Ex: if S

3

+9 is set as -1,000, the integral

value will be -1,000 when it is smaller

than -1,000 and the integration will

stop.