Delta DVP-ES2 User Manual
Page 464
D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
3 - 3 4 8
ASCII mode (M1143 = OFF)
When X0 = ON, MODRW instruction executes the function specified by Function Code 06
PLC
Ö VFD-B, PLC sends: “01 06 2000 1770 52”
VFD-B Ö PLC, PLC receives: “01 06 2000 1770 52”
Registers for data to be sent (sending messages)
Register
Data
Descriptions
D1256 Low byte
‘0’
30 H
ADR 1
D1256 High byte
‘1’
31 H
ADR 0
Device address of VFD-B:
ADR (1,0)
D1257 Low byte
‘0’
30 H
CMD 1
D1257 High byte
‘6’
36 H
CMD 0
Control parameter: CMD (1,0)
D1258 Low byte
‘2’
32 H
D1258 High byte
‘0’
30 H
D1259 Low byte
‘0’
30 H
D1259 High byte
‘0’
30 H
Data Address
D1260 Low byte
‘1’
31 H
D1260 High byte
‘7’
37 H
D1261 Low byte
‘7’
37 H
D1261 High byte
‘0’
30 H
Data
content
H1770 = K6000.
The content of register D50
D1262 Low byte
‘5’
35 H
LRC CHK 1
D1262 High byte
‘2’
32 H
LRC CHK 0
Checksum: LRC CHK (0,1)
Registers for received data (responding messages)
Register
Data
Descriptions
D1070 Low byte
‘0’
30 H
ADR 1
D1070 High byte
‘1’
31 H
ADR 0
D1071 Low byte
‘0’
30 H
CMD 1
D1071 High byte
‘6’
36 H
CMD 0
D1072 Low byte
‘2’
32 H
D1072 High byte
‘0’
30 H
D1073 Low byte
‘0’
30 H
D1073 High byte
‘0’
30 H
Data Address
D1074 Low byte
‘1’
31 H
D1074 High byte
‘7’
37 H
D1075 Low byte
‘7’
37 H
D1075 High byte
‘0’
30 H
Data content
D1076 Low byte
‘6’
36 H
LRC CHK 1
D1076 High byte
‘5’
35 H
LRC CHK 0