D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 3 4 8

ASCII mode (M1143 = OFF)

When X0 = ON, MODRW instruction executes the function specified by Function Code 06

PLC

Ö VFD-B, PLC sends: “01 06 2000 1770 52”

VFD-B Ö PLC, PLC receives: “01 06 2000 1770 52”

Registers for data to be sent (sending messages)

Register

Data

Descriptions

D1256 Low byte

‘0’

30 H

ADR 1

D1256 High byte

‘1’

31 H

ADR 0

Device address of VFD-B:
ADR (1,0)

D1257 Low byte

‘0’

30 H

CMD 1

D1257 High byte

‘6’

36 H

CMD 0

Control parameter: CMD (1,0)

D1258 Low byte

‘2’

32 H

D1258 High byte

‘0’

30 H

D1259 Low byte

‘0’

30 H

D1259 High byte

‘0’

30 H

Data Address

D1260 Low byte

‘1’

31 H

D1260 High byte

‘7’

37 H

D1261 Low byte

‘7’

37 H

D1261 High byte

‘0’

30 H

Data

content

H1770 = K6000.

The content of register D50

D1262 Low byte

‘5’

35 H

LRC CHK 1

D1262 High byte

‘2’

32 H

LRC CHK 0

Checksum: LRC CHK (0,1)

Registers for received data (responding messages)

Register

Data

Descriptions

D1070 Low byte

‘0’

30 H

ADR 1

D1070 High byte

‘1’

31 H

ADR 0

D1071 Low byte

‘0’

30 H

CMD 1

D1071 High byte

‘6’

36 H

CMD 0

D1072 Low byte

‘2’

32 H

D1072 High byte

‘0’

30 H

D1073 Low byte

‘0’

30 H

D1073 High byte

‘0’

30 H

Data Address

D1074 Low byte

‘1’

31 H

D1074 High byte

‘7’

37 H

D1075 Low byte

‘7’

37 H

D1075 High byte

‘0’

30 H

Data content

D1076 Low byte

‘6’

36 H

LRC CHK 1

D1076 High byte

‘5’

35 H

LRC CHK 0