D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 4 4 6

API Mnemonic

Operands

Function

198

D VSPO

Variable speed pulse

output

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S

K H

KnX

KnY KnM KnS T C D E F

S

1

*

S

2

*

*

*

S

3

*

*

*

D

*

DVSPO: 17 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S

1

: Target frequency of output S

2

: Target number of pulses S

3

: Gap time and gap

frequency D: Pulse output device (Y0, Y2)

Explanations:

1.

Max frequency for S

1

: 100kHz. Target frequency can be modified during the execution of

instruction. When S

1

is modified, VSPO will ramp up/down to the target frequency according

to the ramp-up gap time and gap frequency set in S

3.

2.

S

2

target number of pulses is valid only when the instruction is executed first time. S

2

can

NOT be modified during the execution of instruction. S

2

can be a negative value, however, if

the output direction is not specified in D1220/D1221, PLC will take this value as a positive

value. When target number of pulses are specified with 0, PLC will perform continuous

output.

3.

S

3

occupies 2 consecutive 16-bit devices. S

3

+0 stores the gap frequency S

3

+1 stores the gap

time. Parameter setting can be modified during the execution of instruction. Set range for

S

3

+0: 1Hz ~ 32767Hz; set range for S

3

+0: 1ms ~ 80ms. If set value exceeds the available

range, PLC will take the upper or lower bound value.

4.

D pulse output device supports only Y0 and Y2. If Y1 and Y3 is required for output direction

control, D1220 or D1221 has tobe set as K1(Pulse/Dir).

5.

Parameters set in S

3

can only be modified while modifying the value in S

1.

When target

frequency is set as 0, PLC will ramp down to stop according to parameters set in S

3

. When

the output is stopped, PLC will enable the flags indicating pause status (Y0: M1538, Y2:

M1540). If target frequency other than 0 is specified again, pulse output will ramp up to target

frequency and operates untill target number of pulses are completed.