1 . P L C C o n c e p ts

1 - 1 7

Example 2 - Start First latched circuit

When X1 (START) = ON and X2 (STOP) = OFF, Y1 will be ON

and latched. If X2 is turned ON, Y1 remains ON. This is a Start

First circuit because START button has the control priority than

STOP

X2

Y1

X1

Y1



Example 3 - Latched circuit of SET and RST

X2

Y1

X1

SET

Y1

RST

Stop first

The diagram opposite are latched circuits consist of RST and

SET instructions.

In PLC processing principle, the instruction close to the end of

the program determines the final output status of Y1. Therefore,

if both X1 and X2 are ON, RST which is lower than SET forms a

Stop First circuit while SET which is lower than RST forms a

Start First circuit.

X2

Y1

X1

SET

Y1

RST

Start first



Example 4 - Power down latched circuit

The auxiliary relay M512 is a latched relay. Once X1 is ON, Y1

retains its status before power down and resumes after power

up.

X2

M512

X1

SET

RST

M512

Y1

M512



Example 5 - Conditional Control

X3

Y1

X1

Y1

X4

Y2

X2

Y2

Y1

X1

X3

X2

X4

Y1

Y2

Because NO contact Y1 is connected to the circuit of Y2 output, Y1 becomes one of the conditions

for enabling Y2, i.e. for turning on Y2, Y1 has to be ON