D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3-220

6.

When RS instruction is applied for communication between PLC and peripheral devices on

COM2 RS-485, usually STX (Start of the text) and ETX (End of the text) have to be set into

communication format. In this case, b8~10 of D1120 should be set to 1, so that users can set

up STX/ETX as user-defined or system-defined by using M1126, M1130, and D1124~D1126.

For settings of M1126 and M1130, please refer to the following table.

M1130

0

1

0

D1124: user defined

D1125: user defined

D1126: user defined

D1124: H 0002

D1125: H 0003

D1126: H 0000(no setting)

M1

12

6

1

D1124: user defined

D1125: user defined

D1126: user defined

D1124: H 003A(’:’)

D1125: H 000D(CR)

D1126: H 000A(LF)

7.

Example of setting communication format in D1120:

Communication format:

Baud rate: 9600, 7, N, 2

STX : “: “

ETX1 : “CR”

ETX2 : “LF”

Check to the table in point 4 and the set value H788 can be referenced corresponding to the

baud rate. Set the value into D1120.

b15

b0

0

0 0

0

0 1

1

1 1 0 0

0

1 0 0 0

7

8

8

D1120

0

N/A

MOV

H788

D1120

M1002

When STX, ETX1 and ETX2 are applied, care should be taken on setting the ON/OFF status

of M1126 and M1130.

8. D1250(COM1)、D1253(COM3) communication error code:

Value

Error Description

H0001 Communication

time-out

H0002 Checksum

error

H0003

Exception Code exists

H0004

Command code error / data error