Delta DVP-ES2 User Manual
Page 454
D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
3 - 3 3 8
3.
Take the connection between PLC (PLC COM2) and VFD-B for example, the tables below
explains the status when PLC reads status of VFD-B. (M1143 = OFF, ASCII Mode) (M1143 =
ON, RTU Mode)
H87
MOV
M1002
D1120
SET
M1120
K100
MOV
D1129
RST
M1127
Set communication protocol as 9600, 8, E, 1
Retain communication protocol
Set communication timeout as 100ms
MODRW
K3
K1
X0
H2100
D0
K6
Connection device
address: K1
Function code: K3
read multiple words
Data address: H2100
Data storing register
Data length(word)
Processing received data
ASCII mode : The received ASCII data is stored in registers starting from D0
and PLC converts the ASCII data to Hex value and stores them in
D1296~D1301 automatically.
RTU mode : The received data is stored in registers starting from D0 in Hex value.
Reset M1127
M1127
SET
X0
M1122
Sending request
M1143 = OFF
ASCII mode
RST
M1143
M1143 = ON
RTU mode
SET
M1143
Receiving completed
ASCII mode (M1143 = OFF):
When X0 = ON, MODRW instruction executes the function specified by Function Code 03
PLC
Ö VFD-B, PLC sends: “01 03 2100 0006 D5”
VFD-B
Ö PLC, PLC receives: “01 03 0C 0100 1766 0000 0000 0136 0000 3B”
Registers for data to be sent (sending messages)
Register
Data
Descriptions
D1256 Low byte
‘0’
30 H
ADR 1
D1256 High byte
‘1’
31 H
ADR 0
Address of VFD-B: ADR (1,0)
D1257 Low byte
‘0’
30 H
CMD 1
D1257 High byte
‘3’
33 H
CMD 0
Control parameter: CMD (1,0)
D1258 Low byte
‘2’
32 H
D1258 High byte
‘1’
31 H
D1259 Low byte
‘0’
30 H
D1259 High byte
‘0’
30 H
Data Address