D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 3 7 4

API Mnemonic

Operands

Function

159

D DRVA

Absolute Position
Control

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S

K H

KnX

KnY KnM KnS T C D E F

S

1

*

* *

*

*

*

*

*

*

*

*

S

2

*

* *

*

*

*

*

*

*

*

*

D

1

*

D

2

* * *

DRVA: 9 steps

DDRVA: 17 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S

1

: Numbers of pulses (Absolute positioning) S

2

: Pulse output frequency D

1

: Pulse output

device D

2

: Direction signal output

Explanations:

1.

The instruction only supports the pulse output type: Pulse + Direction.

2.

S

1

is the number of pulses (Absolute positioning). Available range: -2,147,483,648 ~

+2,147,483,647. “+/-” signs indicate forward and reverse direction.

3.

S

2

is the pulse output frequency. Available range: 6 ~ 100,000Hz.

4.

D

1

is the pulse output device. It can designate CH0 (Y0) and CH1 (Y2).

5.

D

2

is the direction signal output device. If Y output is designated, only CH0 (Y1) and CH1 (Y3)

are available.

6.

S

1

is the target position for absolute positioning. The actual number of output pulses (S

1

current position) will be calculated by PLC. When the result is positive, pulse output executes

forward operation, i.e. D

2

= OFF; when the results is negative, pulse output executes reverse

operation, i.e. D

2

= ON.

7.

The set value in S

1

is the absolute position from zero point. The calculated actual number of

output pulses will be the relative position of

- current position (32-bit data) of CH0 (Y0, Y1) which is stored in D1031(high), D1030 (low)

- current position (32-bit data) of CH1 (Y2, Y3) which is stored in D1337(high), D1336 (low).

In reverse direction pulse output, value in (D1031, D1330) and (D1336, D1337) decreases.

8.

D1343 (D1353) is the ramp up/down time (between start frequency and pulse output

frequency) setting of CH0 (CH1). Available range: 20 ~ 32,767ms. Default: 100ms. PLC will

take 20ms as the set value when specified value is below 20ms or above 32,767ms.

9.

D1340 (D1352) is start/end frequency setting of CH0 (CH1). Available range: 6 ~ 32,767Hz.

PLC will take the start/end frequency as the pulse output frequency when pulse output

frequency S

2

is smaller or equals the start/end frequency.