7 C AN o p e n F u n c t i o n a n d O p e r a t i o n
7 - 2 5
D9998 can be used for monitoring the state of nodes from 1 to 16 in the network. And the 16
bits of D9998 corresponds to 16 slaves and the corresponding relations of them are shown
below.
Bit
b7
b6
b5
b4
b3
b2
b1
b0
Node
Node 8
Node 7
Node 6
Node 5
Node 4
Node 3
Node 2
Node 1
Bit
b15
b14
b13
b12
b11
b10
b9
b8
Node Node16
Node15
Node14
Node13
Node12
Node11
Node10 Node
9
When the node in the master node list is normal, the corresponding bit is OFF; when the node
in the master node list is abnormal (E.g. Initializing fails or slave is offline due to other
abnormality), the corresponding bit is ON.
¾
The error code of every node is displayed through the corresponding special register and the
relations between special register and corresponding node are shown below.
Special
register
D9981
D9982
D9983
D9984
D9985
D9986
D9987
D9988
Node
Node 1 Node 2
Node 3
Node 4
Node 5
Node 6
Node 7
Node 8
Special
register
D9989
D9990
D9991
D9992
D9993
D9994
D9995
D9996
Node Node
9
Node10
Node11
Node12
Node13
Node14
Node15
Node16
¾
Code display in D9981~D9996 as DVP32ES2-C is in master mode:
Code
Indication
How to correct
E0
DVP-ES2-C master module
receives the emergency
message sent from slave.
Read the relevant message via PLC program
E1
PDO data length returned from
the slave is not consistent with
the length set in the node list.
Set the PDO data length of slave and
re-download them.
E2
PDO of slave is not received.
Check and ensure the setting is correct.
E3
Downloading auto SDO fails.
Check and ensure auto SDO is correct.
E4
Configuration of PDO parameter
fails.
Ensure that the PDO parameter setting is
legal.
E5
Error in key parameter setting.
Ensure that the actually connected slave is
consistent with the configured slave.
E6
The slave does not exist in the
network
E7
Slave error control is timed-out.
Ensure that the supply power of slave is
normal and the connection in the network is
proper.