D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 1 7 0

API Mnemonic

Operands

Function

67

D RAMP

Ramp variable
Value

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T C D E F

S

1

*

S

2

*

D

*

n

*

*

*

RAMP: 9 steps

DRAMP: 17 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S

1

: Start of ramp signal S

2

: End of ramp signal D: Current value of ramp signal (occupies 2

consecutive devices) n: Times for scan (n: 1~32,767)

Explanations:

147. This instruction creates a ramp output. A ramp output linearity depends on a consistent scan

time. Therefore, scan time has to be fixed before executing RAMP instruction.

148. When RAMP instruction is executed, the ramp signal will vary from S

1

to S

2

. Current value of

ramp signal is stored in D and D+1 stores the current number of accumulated scans. When

ramp signal reaches S

2

, or when the drive contact of RAMP instruction turns OFF, the content

in D varies according to the setting of M1026 which is explained later in Points to note.

149. When n specifies a D register, the value in D cannot be modified during the execution of the

instruction. Please modify the content of D when the instruction is stopped.

150. When this instruction is applied with analog output function, Ramp start and Ramp stop

function can be achieved.

Program example:

1.

Before executing the instruction, first drive M1039 = ON to fix the scan time. Use MOV

instruction to write the fixed scan time to the special data register D1039. Assume the scan

time is 30ms and take the below program for example, n = K100, the time for D10 to increase

to D11 will be 3 seconds (30ms × 100).

2.

When X20 goes OFF, the instruction will stop its execution. When X10 goes ON again, the

content in D12 will be reset to 0 for recalculation

3.

When M1026 = OFF, M1029 will be ON to indicate the completion of ramp process and the

content in D12 will be reset to the set value in D10.

4.

Set the Start and End of ramp signal in D10 and D11. When X20 = ON, D10 increases towards

D11, the current value of the variation is stored in D12 and the number of current scans is

stored in D13.

X20

RAMP

D10

D11

D12

K100