D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3-268

API Mnemonic

Operands

Function

100

MODRD

Read Modbus Data

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T C D E F

S

1

*

*

*

S

2

*

*

*

n

*

*

*

MODRD: 7 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S

1

: Device address (K0~K254) S

2

: Data address n: Data length (K1<n≦K6)

Explanations:

1.

MODRD instruction supports COM2 (RS-485).

2.

MODRD is an instruction exclusively for peripheral communication equipment in MODBUS

ASCII/RTU mode. The built-in RS-485 communication ports in Delta VFD drives (except for

VFD-A series) are all compatible with MODBUS communication format. MODRD can be used

for communication (read data) of Delta drives.

3.

If the address of S

2

is illegal for the designated communication device, the device will respond

with an error, PLC will record the error code in D1130 and M1141 will be ON.

4.

The feedback (returned) data from the peripheral equipment will be stored in D1070 ~ D1085.

After data receiving is completed, PLC will check the validity of the data automatically. If there

is an error, M1140 will be ON.

5.

The feedback data are all ASCII codes in ASCII mode, so PLC will convert the feedback data

into hex data and store them in D1050 ~ D1055. D1050 ~ D1055 is invalid in RTU mode.

6.

If peripheral device receives a correct record (data) from PLC after M1140/M1141 = ON, the

peripheral device will send out feedback data and PLC will reset M1140/M1141 after the

validity of data is confirmed.

7.

There is no limitation on the times of using this instruction, but only one instruction can be

executed at a time on the same COM port.

8.

Rising-edge contact (LDP, ANDP, ORP) and falling-edge contact (LDF, ANDF, ORF) can not

be used with MODRD instruction, otherwise the data stored in the receiving registers will be

incorrect.

9.

For associated flags and special registers, please refer to Points to note of API 80 RS

instruction.