3 . I n s t r u c t i o n S e t

3 - 3 5 3

Registers

for data to be sent (sending messages)

Register

Data

Descriptions

D1256 下 01

H

Address

D1257 下 0F

H

Function

D1258 下 05

H

D1259 下 00

H

Data Address

D1260 下 00

H

D1261 下 10

H

Number of Data(count by bit)

D1262 下

02 H

Byte Count

D1263 下

34 H

Data content 1

Content of D0: H34

D1264 下

12 H

Data content 2

Content of D1: H12

D1265 下

21 H

CRC CHK Low

D1266 下

ED H

CRC CHK High

Registers for received data (responding messages)

Register

Data

Descriptions

D1070 下 01

H

Address

D1071 下 0F

H

Function

D1072 下 05

H

D1073 下 00

H

Data Address

D1074 下 00

H

D1075 下 10H

Number of Data(count by bit)

D1076 下

54H

CRC CHK Low

D1077 下

CB H

CRC CHK High

Program example 10: COM1 (RS-232) / COM3 (RS-485), Function Code H0F

1.

Function code K15 (H0F): write in multiple bit devices. Up to 64 bits can be written

2.

PLC1 connects to PLC2: (M1143 = OFF, ASCII mode), (M1143 = ON, RTU mode)

3.

PLC COM1/COM3 will not process the received data.

4.

Take the connection between PLC1 (PLC COM3) and PLC2 (PLC COM1) for example, the

tables below explain the status when PLC1 force ON/OFF Y0~Y17 of PLC2.

Set value: K4Y0=1234H

Device

Status

Device

Status

Device

Status

Device

Status

Y0 OFF

Y1 OFF

Y2 ON Y3 OFF

Y4 ON Y5 ON Y6 OFF

Y7 OFF

Y10 OFF Y11 ON Y12 OFF Y13 OFF

Y14 ON Y15 OFF Y16 OFF Y17 OFF

z

If PLC applies COM1 for communication, the below program can be usable by changing:

1. D1109→D1036: communication protocol

2. M1136→M1138: retain communication setting