Points to note:

175. When HKY instruction is executed, 8 scan cycles (matrix scan) are required for reading the

input value successfully. A scan cycle that is too long or too short may cause the input to be

read incorrectly. In this case we suggest the following solutions:

If the scan cycle is too short, I/O may not be able to respond in time, resulting in incorrect input

values. To solve this problem please fix the scan time.

If the scan period is too long, the key may respond slowly. In this case, write this instruction into

the time-interrupt subroutine to fix the execution time for this instruction.

176. The function of flag M1167:

When M1167 = ON, HKY instruction can input hexadecimal value consists of 0~F.

When M1167 = OFF, A~F of HKY instruction are used as function keys.

‹