Points to note:

1.

There are two methods to correct built-in RTC:

z

Correcting by API167 TWR instruction

Please refer to explanation of instruction TWR (API 167)

z

Setting by peripheral device

Using WPLSoft / ISPSoft (Ladder editor)

2.

Display 4-digit year data:

z

D1319 only stores the 2-digit year in A.D. If 4-digit year data is required, please insert the

following instruction at the start of program.

M1002

SET

M1016

Display 4-digit year data

z

The original 2-digit year will be switched to a 4-digit year, i.e. the 2-digit year will pluses

2,000. If users need to write in new time in 4-digit year display mode, only a 2-digit year

data is applicable (0 ~ 99, indicating year 2000 ~ 2099). For example, 00 = year 2000, 50

= year 2050 and 99 = year 2099.

z

Flags and special registers for RTC

Device

Content

Function

M1016 Year

display

mode of RTC

OFF: D1319 stores 2-digit year data in A.D.

ON: D1319 stores 2-digit year data in A.D + 2000

M1017

±30 seconds

correction on

RTC

Correction takes place when M1017 goes from OFF to

ON (Second data in 0 ~ 29: reset to 0. Second data in

30 ~ 59: minute data pluses 1, second data resets)

Device

Content

Range

D1313 Second

0-59

D1314 Minute

0-59

D1315 Hour

0-23

D1316 Day

1-31

D1317 Month

1-12

D1318

Day (Mon. ~ Sun.)

1-7

D1319

Year

0-99 (two digit year data)