4 command code: 05, force on/off single contact, Command code: 05, force on/off single contact -16 – Delta DVP-ES2 User Manual
Page 618
D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
Field Name
ASCII
Data Hi (T26)
00
Data Lo (T26)
07
Data Hi (T27)
00
Data Lo (T27)
08
Error Check (LRC)
C8
END 1
0D (Hex)
END 0
0A (Hex)
4.5.4 Command Code: 05, Force ON/OFF single contact
The Force data FF00 (Hex) indicates force ON the contact. The Force data 0000 (Hex) indicates force
OFF the contact. Also, When MMNN = 0xFF00, the coil will be ON, when MMNN = 0x0000, the coil will
be OFF. Other force data is invalid and will not take any effect.
Example: Force coil Y0 ON
PC→PLC “: 01 05 05 00 FF 00 F6 CR LF”
Sent message:
Field Name
ASCII
STX :
Slave Address
01
Command code
05
Coil Address Hi
05
Coil Address Lo
00
Force Data Hi
FF
Force Data Lo
00
Error Check (LRC)
F6
END 1
0D (Hex)
END 0
0A (Hex)
PLC→PC “: 01 05 05 00 FF 00 F6 CR LF”
Feedback message:
Field Name
ASCII
STX :
Slave Address
01
Command code
05
Coil Address Hi
05
Coil Address Lo
00
Force Data Hi
FF
4 - 1 6