beautypg.com

Delta DVP-ES2 User Manual

Page 76

background image

D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

2-44

Special

D

Content

ES2
EX2

SS

2

SA

2

SX

2

OFF

Ø

ON

STOP

Ø

RUN

RUN

Ø

STOP

Attrib.

Latch

-ed

Default

D1253

COM3 (RS-485) communication error code (only
applicable for MODRW/RS instruction)

0 - -

R/W

NO

0

D1255* COM3 (RS-485) PLC communication address

50

- -

R/W

YES

1

D1256

D1295

For COM2 RS-485 MODRW instruction.
D1256~D1295 store the sent data of MODRW
instruction. When MODRW instruction sends out
data, the data will be stored in D1256~D1295.
Users can check the sent data in these registers.

0 - - R

NO 0

D1296

D1311

For COM2 RS-485 MODRW instruction.
D1296~D1311 store the converted hex data from
D1070 ~ D1085 (ASCII). PLC automatically
converts the received ASCII data in D1070 ~
D1085 into hex data.

0 - - R

NO 0

D1312*

Specify the number of additional pulses for
additional pulses output and Z-phase seeking
function of ZRN instruction (Has to be used with
M1308)

0 0 -

R/W

NO 0

D1313* Second of RTC: 00 ~ 59

- - -

R/W

YES

0

D1314* Minute of RTC: 00 ~ 59

- - -

R/W

YES

0

D1315* Hour of RTC: 00 ~ 23

- - -

R/W

YES

0

D1316* Day of RTC: 01 ~ 31

- - -

R/W

YES

1

D1317* Month of RTC: 01 ~ 12

- - -

R/W

YES

1

D1318* Week of RTC: 1 ~ 7

- - -

R/W

YES

2

D1319* Year of RTC: 00 ~ 99 (A.D.)

- - -

R/W

YES

8

D1320* ID of the 1

st

right side module

0 - - R

NO 0

D1321* ID of the 2

nd

right side module

0 - - R

NO 0

D1322* ID of the 3

rd

right side module

0 - - R

NO 0

D1323* ID of the 4

th

right side module

0 - - R

NO 0

D1324* ID of the 5

th

right side module

0 - - R

NO 0

D1325* ID of the 6

th

right side module

0 - - R

NO 0

D1326* ID of the 7

th

right side module

0 - - R

NO 0

D1327* ID of the 8

th

right side module

0 - - R

NO 0

D1336 PV of Y2 pulse output (Low word)

- - -

R/W

YES

0

D1337 PV of Y2 pulse output (High word)

- - -

R/W

YES

0

D1338 PV of Y3 pulse output (Low word)

- - -

R/W

NO

0

D1339 PV of Y3 pulse output (High word)

- - -

R/W

NO

0

D1340

Start/end frequency of the 1

st

group pulse output

CH0 (Y0, Y1)

100

- -

R/W

NO

100

D1343

Ramp up/down time of the 1

st

group pulse output

CH0 (Y0, Y1)

100

- -

R/W

NO

100

D1348*

When M1534 = ON, D1348 stores the ramp-down
time of CH0(Y0, Y1) pulse output.

100

- -

R/W

NO

100

D1349*

When M1535 = ON, D1349 stores the ramp-down
time of CH1(Y2, Y3) pulse output.

100

- -

R/W

NO

100

This manual is related to the following products: