Delta DVP-ES2 User Manual
Page 76
D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
2-44
Special
D
Content
ES2
EX2
SS
2
SA
2
SX
2
OFF
Ø
ON
STOP
Ø
RUN
RUN
Ø
STOP
Attrib.
Latch
-ed
Default
D1253
COM3 (RS-485) communication error code (only
applicable for MODRW/RS instruction)
○
╳
○
╳
0 - -
R/W
NO
0
D1255* COM3 (RS-485) PLC communication address
○
╳
○
○
50
- -
R/W
YES
1
D1256
↓
D1295
For COM2 RS-485 MODRW instruction.
D1256~D1295 store the sent data of MODRW
instruction. When MODRW instruction sends out
data, the data will be stored in D1256~D1295.
Users can check the sent data in these registers.
○
○
○
○
0 - - R
NO 0
D1296
↓
D1311
For COM2 RS-485 MODRW instruction.
D1296~D1311 store the converted hex data from
D1070 ~ D1085 (ASCII). PLC automatically
converts the received ASCII data in D1070 ~
D1085 into hex data.
○
○
○
○
0 - - R
NO 0
D1312*
Specify the number of additional pulses for
additional pulses output and Z-phase seeking
function of ZRN instruction (Has to be used with
M1308)
○
╳
○
○
0 0 -
R/W
NO 0
D1313* Second of RTC: 00 ~ 59
○
○
○
○
- - -
R/W
YES
0
D1314* Minute of RTC: 00 ~ 59
○
○
○
○
- - -
R/W
YES
0
D1315* Hour of RTC: 00 ~ 23
○
○
○
○
- - -
R/W
YES
0
D1316* Day of RTC: 01 ~ 31
○
○
○
○
- - -
R/W
YES
1
D1317* Month of RTC: 01 ~ 12
○
○
○
○
- - -
R/W
YES
1
D1318* Week of RTC: 1 ~ 7
○
○
○
○
- - -
R/W
YES
2
D1319* Year of RTC: 00 ~ 99 (A.D.)
○
○
○
○
- - -
R/W
YES
8
D1320* ID of the 1
st
right side module
○
╳
╳
╳
0 - - R
NO 0
D1321* ID of the 2
nd
right side module
○
╳
╳
╳
0 - - R
NO 0
D1322* ID of the 3
rd
right side module
○
╳
╳
╳
0 - - R
NO 0
D1323* ID of the 4
th
right side module
○
╳
╳
╳
0 - - R
NO 0
D1324* ID of the 5
th
right side module
○
╳
╳
╳
0 - - R
NO 0
D1325* ID of the 6
th
right side module
○
╳
╳
╳
0 - - R
NO 0
D1326* ID of the 7
th
right side module
○
╳
╳
╳
0 - - R
NO 0
D1327* ID of the 8
th
right side module
○
╳
╳
╳
0 - - R
NO 0
D1336 PV of Y2 pulse output (Low word)
○
○
○
○
- - -
R/W
YES
0
D1337 PV of Y2 pulse output (High word)
○
○
○
○
- - -
R/W
YES
0
D1338 PV of Y3 pulse output (Low word)
○
○
○
○
- - -
R/W
NO
0
D1339 PV of Y3 pulse output (High word)
○
○
○
○
- - -
R/W
NO
0
D1340
Start/end frequency of the 1
st
group pulse output
CH0 (Y0, Y1)
○
○
○
○
100
- -
R/W
NO
100
D1343
Ramp up/down time of the 1
st
group pulse output
CH0 (Y0, Y1)
○
○
○
○
100
- -
R/W
NO
100
D1348*
When M1534 = ON, D1348 stores the ramp-down
time of CH0(Y0, Y1) pulse output.
○
○
○
○
100
- -
R/W
NO
100
D1349*
When M1535 = ON, D1349 stores the ramp-down
time of CH1(Y2, Y3) pulse output.
○
○
○
○
100
- -
R/W
NO
100