Delta DVP-ES2 User Manual
Page 582
D V P - E S 2 / S X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l – P r o g r a m m i n g
3 - 4 6 6
API Mnemonic
Operands
Function
207
CSFO
Catch speed and
proportional output
Controllers
ES2
EX2
SS2
SA2 SX2 SE
Bit Devices
Word devices
Program Steps
Type
OP
X Y M S K H
KnX
KnY KnM KnS T C D E F
S
*
S
1
*
D
*
CSFO: 7 steps
PULSE 16-bit 32-bit
ES2/
EX2
SS2 SA2 SX2 SE
ES2/
EX2
SS2 SA2 SX2 SE
ES2/
EX2
SS2 SA2 SX2 SE
Operands:
S: Source device of signal input (Only X0~X3 are available) S
1
: Sample time setting and the
input speed information D: Output proportion setting and output speed information
Explanations:
1. When
S specifies X0, PLC only uses X0 input point and its associated high speed pulse output:
Y0, in this case Y1 is normal output point. When S specifies X1, PLC uses X0 (A phase) and
X1 (B phase) input points and their associated output: Y0 (Pulse) / Y1 (Dir). When S specifies
X2, PLC only uses X2 input point and its associated high speed pulse output: Y2, in this case
Y3 is normal output point. When S specifies X3, PLC uses X2 (A phase) and X3 (B phase)
input points and their associated output: Y2 (Pulse) / Y3 (Dir).
2.
The execution of CSFO requires hardware high speed counter function as well as the high
speed output function. Therefore, when program scan proceeds to CSFO instruction with high
speed counter input points (X0, X1) or (X2, X3) enabled by DCNT instruction, or high speed
pulse outputs (Y0, Y1) or (Y2, Y3) enabled by other high speed output instructions, CSFO
instruction will not be activated.
3. If
S specifies X1 / X3 with 2-phase 2 inputs, the counting mode is fixed as quadruple
frequency.
4.
During pulse output process of Y0 or Y2, special registers (D1031, D1330 / D1337, D1336)
storing the current number of output pulses will be updated when program scan proceeds to
this instruction.
5.
S
1
occupies consecutive 4 16-bit registers. S
1
+0 specifies the sampling times, i.e. when S
1
+0
specifies K1, PLC catches the speed every time when 1 pulse is outputted. Valid range for S
1
+0 in 1-phase 1-input mode: K1~K100, and 2-phase 2-input mode: K2~K100. If the specified
value exceeds the valid range, PLC will take the lower/upper bound value as the set value.
Sample time can be changed during PLC operation, however the modified value will take
effect until program scan proceeds to this instruction. S
1
+1 indicates the latest speed sampled
by PLC (Read-only). Unit: 1Hz. Valid range:
±10kHz. S
1
+2 and S
1
+3 indicate the accumulated
number of pulses in 32-bit data (Read-only).