D V P - E S 2 / S X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l – P r o g r a m m i n g

3 - 4 6 6

API Mnemonic

Operands

Function

207

CSFO

Catch speed and
proportional output

Controllers

ES2
EX2

SS2

SA2 SX2 SE

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T C D E F

S

*

S

1

*

D

*

CSFO: 7 steps

PULSE 16-bit 32-bit

ES2/

EX2

SS2 SA2 SX2 SE

ES2/

EX2

SS2 SA2 SX2 SE

ES2/

EX2

SS2 SA2 SX2 SE

Operands:

S: Source device of signal input (Only X0~X3 are available) S

1

: Sample time setting and the

input speed information D: Output proportion setting and output speed information

Explanations:

1. When

S specifies X0, PLC only uses X0 input point and its associated high speed pulse output:

Y0, in this case Y1 is normal output point. When S specifies X1, PLC uses X0 (A phase) and

X1 (B phase) input points and their associated output: Y0 (Pulse) / Y1 (Dir). When S specifies

X2, PLC only uses X2 input point and its associated high speed pulse output: Y2, in this case

Y3 is normal output point. When S specifies X3, PLC uses X2 (A phase) and X3 (B phase)

input points and their associated output: Y2 (Pulse) / Y3 (Dir).

2.

The execution of CSFO requires hardware high speed counter function as well as the high

speed output function. Therefore, when program scan proceeds to CSFO instruction with high

speed counter input points (X0, X1) or (X2, X3) enabled by DCNT instruction, or high speed

pulse outputs (Y0, Y1) or (Y2, Y3) enabled by other high speed output instructions, CSFO

instruction will not be activated.

3. If

S specifies X1 / X3 with 2-phase 2 inputs, the counting mode is fixed as quadruple

frequency.

4.

During pulse output process of Y0 or Y2, special registers (D1031, D1330 / D1337, D1336)

storing the current number of output pulses will be updated when program scan proceeds to

this instruction.

5.

S

1

occupies consecutive 4 16-bit registers. S

1

+0 specifies the sampling times, i.e. when S

1

+0

specifies K1, PLC catches the speed every time when 1 pulse is outputted. Valid range for S

1

+0 in 1-phase 1-input mode: K1~K100, and 2-phase 2-input mode: K2~K100. If the specified

value exceeds the valid range, PLC will take the lower/upper bound value as the set value.

Sample time can be changed during PLC operation, however the modified value will take

effect until program scan proceeds to this instruction. S

1

+1 indicates the latest speed sampled

by PLC (Read-only). Unit: 1Hz. Valid range:

±10kHz. S

1

+2 and S

1

+3 indicate the accumulated

number of pulses in 32-bit data (Read-only).