2 . P r o g r a m m i n g C o n c e p ts

2.

D1008 saves the STEP address where the timeout occurred

Scan Time Monitor

Function Group

D1010~D1012

Number

Contents:

The present value, minimum value and maximum value of scan time are stored in D1010 ~ D1012.

D1010: current scan time

D1011: minimum scan time

D1012: maximum scan time

Internal Clock Pulse

Function Group

M1011~M1014

Number

Contents:

1.

PLC provides four different clock pulses to aid the application. When PLC is power-on, the

four clock pulses will start automatically.

M1011 (10 ms)

M1012 (100 ms)

M1013 (1 sec)

M1014 (60 sec)

100 Hz

10 Hz

1 Hz

10 ms

100 ms

1 sec

1 min

2.

Clock pulse works even when PLC stops, i.e. activation of clock pulse is not synchronized

with PLC RUN execution.

High-speed Timer

Function Group

M1015, D1015

Number

Contents:

1.

When M1015 = ON, high-speed timer D1015 will be activated when the current scan

proceeds to END instruction. The minimum resolution of D1015 is 100us.

2.

The range of D1015 is 0~32,767. When it counts to 32,767, it will start from 0 again.

3.

When M1015 = OFF, D1015 will stop timing immediately.

Example:

1.

When X10 = ON, M1015 = ON to start high-speed timer and record the present value in

D1015.

2.

When X10 = OFF, M1015 = OFF. High-speed timer is disabled.

2 - 5 7