beautypg.com

Delta DVP-ES2 User Manual

Page 132

background image

D V P - E S 2 / S A 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 1 6

supports index E and F.

A

symbol

* is given to device which can be used for this operand

Steps occupied by the 16-bit/32-bit/pulse instruction

Applicable PLC models for 16-bit/32-bit/pulse execution instruction.

Continuous execution vs. Pulse execution

1.

There are two execution types for instructions: continuous execution instruction and pulse

instruction. Program scan time is shorter when instructions are not executed. Therefore,

using the pulse execution instruction can reduce the scan time of the program.

2.

The ‘pulse’ function allows the associated instruction to be activated on the rising edge of the

drive contact. The instruction is driven ON for the duration of one program scan.

3.

In addition, while the control input remains ON, the associate instruction will not be executed

for the second time. To re-execute the instruction the control input must be turned from OFF

to ON again.

Pulse execution instruction

X0

D10

D12

MOVP

When X0 goes from OFF to ON, MOVP

instruction will be executed once and the

instruction will not be executed again in the scan

period

Continuous execution instruction

X1

D10

D12

MOV

When X1=ON, the MOV instruction can be

re-executed again in every scan of program. This

is called continuous execution instruction.

Operands

1.

Bit devices X, Y, M, and S can be combined into word device, storing values and data for

operations in the form of KnX, KnY, KnM and KnS in an application instruction.

2.

Data register D, timer T, counter C and index register E, F are designated by general

operands.

3.

A data register D consists of 16 bits, i.e. a 32-bit data register consists of 2 consecutive D

registers.

4.

If an operand of a 32-bit instruction designates D0, 2 consecutive registers D1 and D0 will be

occupied. D1 is thehigh word and D0 is the low word. This proncipal also applys to timer T

and 16-bit counters C0 ~ C199.

5.

When the 32-bit counters C200 ~ C255 are used as data registers, they can only be

designataed by the operands of 32-bit instructions.

Operand Data format

This manual is related to the following products: