D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

2.

The default in the monitor timer is 200ms. If the program is long or the operation is too

complicated, MOV instruction can be used to modify SV. See the example below for SV =

300ms.

M1002

0

MOV

K300

D1000

Initial pulse

3.

The maximum SV in the monitor timer is 32,767ms. However, care should be taken when

adjusting SV. If SV in D1000 is too big, it cost much longer for operation errors to be detected.

Therefore, SV is suggested to be shorter than 200ms.

4.

Scan time could be prolonged due to complicated instruction operations or too many I/O

modules being connected. Check D1010 ~ D1012 to see if the scan time exceeds the SV in

D1000. Besides modifying the SV in D1000, users can also apply WDT instruction (API 07).

When program execution progresses to WDT instruction, the internal monitor timer will be

reset and therefore the scan time will not exceed the set value in the monitor timer.

Program Capacity

Function Group

D1002

Number

Contents:

This register holds the program capacity of the PLC.

SS2: 7,920 steps (Word)

ES2 / EX2 / SA2 / SX2 series: 15,872 steps (Word)

Syntax Check

Function Group

M1004, D1004, D1137

Number

Contents:

1.

When errors occur in syntax check, ERROR LED indicator will flash and special relay M1004

= ON.

2.

Timings for PLC syntax check:

a) When the power goes from “OFF” to “ON”.

b) When WPLSoft writes the program into PLC.

c) When on-line editing is being conducted on WPLSoft.

3.

Errors might result from parameter error or grammar error. The error code of the error will be

placed in D1004. The address where the fault is located is saved in D1137. If the error

belongs to loop error it may not have an address associated with it. In this case the value in

D1137 is invalid.

4.

For syntax error codes pease refer to section 6.2 Error Code table.

Watchdog Timer

Function Group

M1008, D1008

Number

Contents:

1.

When the scan is time-out during execution, ERROR LED will be ON and M1008 = ON.

2-56