D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 4 4 4

100KHz

D1340

D1348

D1343

C243 =K50000

600ms

Frequency

Y0 output stops

Time
Pulse number

Specified number of output pulses: 50,500

Actual number of output pulses (D1030, D1031) = K50,560

5. Observe the results of the second execution:

a)

The actual output number 50,560 – specified output number 50,500 = 60

b)

60 x (1/100Hz) = 600ms (idle time)

c)

600ms is an appropriate value. Therefore, set the percentage value (D1131) as

K101 to complete the design.

Points to note:

1. Associated

flags:

M1029

CH0 (Y0, Y1) pulse output execution completed.

M1102

CH1 (Y2, Y3) pulse output execution completed.

M1078

M1078 = ON, CH0 (Y0, Y1) pulse output pause (immediate)

M1104

M1104 = ON CH1 (Y2, Y3) pulse output pause (immediate)

M1108

CH0 (Y0, Y1) pulse output pause (ramp down). M1108 = ON during ramp down.

M1110

CH1 (Y2, Y3) pulse output pause (ramp down). M1110 = ON during ramp down.

M1156

Enabling the mask and alignment mark function on I400/I401(X4) corresponding

to Y0.

M1158

Enabling the mask and alignment mark function on I600/I601(X6) corresponding

to Y2.

M1538

Indicating pause status of CH0 (Y0, Y1).M1538 = ON when output paused.

M1540

Indicating pause status of CH1 (Y2, Y3). M1540 = ON when output paused

M1305

Reverse CH0 (Y0, Y1) pulse output direction. M1305 = ON, pulse output direction

is reversed.

M1306

Reverse CH1 (Y2, Y3) pulse output direction. M1306 = ON, pulse output direction

is reversed

M1347

Auto-reset CH0 (Y0, Y1) when high speed pulse output completed. M1347 will be