beautypg.com

Delta DVP-ES2 User Manual

Page 73

background image

2 . P r o g r a m m i n g C o n c e p ts

2 - 4 1

Special

D

Content

ES2
EX2

SS

2

SA

2

SX

2

OFF

Ø

ON

STOP

Ø

RUN

RUN

Ø

STOP

Attrib.

Latch

-ed

Default

D1070

D1085

Feedback data (ASCII) of Modbus
communication. When PLC’s RS-485
communication instruction receives feedback
signals, the data will be saved in the registers
D1070~D1085. Usres can check the received
data in these registers.

0 - - R

NO

0

D1086

High word of the password in DVP-PCC01

(displayed in hex according to its ASCII codes)

0 - -

R/W

NO

0

D1087

Low word of the password in DVP-PCC01
(displayed in hex according to its ASCII codes)

0 - -

R/W

NO

0

D1089

D1099

Sent data of Modbus communication.

When PLC’s RS-485 communication instruction
sends out data, the data will be stored in
D1089~D1099. Users can check the sent data in
these registers.

0 - - R

NO

0

D1109* COM3 (RS-485) Communication protocol

H’86

- -

R/W

NO

H’86

D1110*

Average value of EX2/SX2 analog input channel 0
(AD 0) When average times in D1062 is set to 1,
D1110 indicates present value.

0 - - R

NO

0

D1111*

Average value of EX2/SX2 analog input channel 1
(AD 1) When average times in D1062 is set to 1,
D1111 indicates present value

0 - - R

NO

0

D1112*

Average value of EX2/SX2 analog input channel 2
(AD 2) Whenaverage times in D1062 is set to 1,
D1112 indicates present value

0 - - R

NO

0

Average value of 20EX2/SX2 analog input
channel 3 (AD 3) Whenaverage times in D1062 is
set to 1, D1113 indicates present value

0 - - R

NO

0

D1113*

Displaying the status of the analog input channel
of 30EX2

0 - - R

NO

0

D1114*

Enable/disable 20EX2/SX2 AD channels
(0: enable (default) / 1: disable)

bit0~bit3 sets AD0~AD3.

P.S. 30EX2 does not support this function.

0 - -

R/W

YES

0

20EX2/SX2 analog input/output mode setting

0 0 0

R/W

YES

0

D1115*

30EX2 analog input/output mode setting

- - -

R/W

YES H’FFFF

D1116*

Output value of analog output channel 0 (DA 0) of
EX2/SX2

0 0 0

R/W

NO

0

D1117*

Output value of analog output channel 1 (DA 0) of
20EX2/SX2

P.S. 30EX2 does not support this function.

0 0 0

R/W

NO

0

D1118*

EX2/SX2 sampling time of analog/digital
converstion. Default: 2. Unit: 1ms. Sampling time
will be regarded as 2ms if D1118≦2

2 - -

R/W

YES

2

D1120* COM2 (RS-485) communication protocol

H’86

- -

R/W

NO

H’86

D1121*

COM1(RS-232) and COM2(RS-485) PLC
communication address

- - -

R/W

Yes

1

D1122

COM2(RS-485) Residual number of words of
transmitting data

0 0 - R

NO

0

D1123

COM2(RS-485) Residual number of words of the
receiving data

0 0 - R

NO

0

This manual is related to the following products: