3 . I n s t r u c t i o n S e t

3 - 4 7 3

API Mnemonic Operands

Function

240~

246

D

OR※

Parallel Type Comparison

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y

M S K H KnX KnY KnM KnS T C D E F

S

1

* *

*

*

*

*

*

*

*

*

*

S

2

* *

*

*

*

*

*

*

*

*

*

OR※: 5 steps

DOR※: 9 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S

1

: Source device 1 S

2

: Source device 2

Explanations:

1.

This instruction compares the content in S

1

and S

2

. Take API240 (OR =) for example, if the

result is “=”, the continuity of the instruction is enabled. If the result is “

≠”, the continuity of the

instruction is disabled

2. OR※ (※: =, >, <, <>,

≤, ≥) instruction is used for parallel connection with contacts.

API No.

16-bit

instruction

32-bit

instruction

Continuity

condition

Discontinuity

condition

240

OR=

DOR=

S

1

S

2

S

1

S

2

241

OR>

DOR>

S

1

S

2

S

1

S

2

242

OR<

DOR<

S

1

S

2

S

1

S

2

244

OR<>

DOR<>

S

1

S

2

S

1

S

2

245

OR<=

DOR<=

S

1

S

2

S

1

S

2

246

OR>=

DOR>=

S

1

S

2

S

1

S

2

3.

When the MSB (16-bit instruction: b15, 32-bit instruction: b31) of S

1

and S

2

is 1, the

comparison value will be viewed as a negative value in comparison..

4.

When 32-bit counters (C200 ~ C254) are used in this instruction, make sure to adopt 32-bit

instruction (DOR※). If 16-bit instruction (OR※) is adopted, a “program error” will occur and

the ERROR indicator on the MPU panel will flash

Program Example:

M60 will be ON either when both X2 and M30 are “ON”, or when the content in 32-bit register D100

(D101)

≥ K100,000.

DOR>=

D100

K100000

X2

M30

M60