2 error code table (hex), Error code table (hex) -4 – Delta DVP-ES2 User Manual
Page 654
D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
6-4
6.2 Error code Table (Hex)
After you write the program into the PLC, the illegal use of operands (devices) or incorrect syntax in
the program will result in flashing of ERROR indicator and M1004 = ON. In this case, you can find
out the cause of the error by checking the error code (hex) in special register D1004. The address
where the error occurs is stored in the data register D1137. If the error is a general loop error, the
address stored in D1137 will be invalid.
Error code
Description
Action
0001
Operand bit device S exceeds the valid range
0002
Label P exceeds the valid range or duplicated
0003
Operand KnSm exceeds the valid range
0102
Interrupt pointer I exceeds the valid range or duplicated
0202
Instruction MC exceeds the valid range
0302
Instruction MCR exceeds the valid range
0401
Operand bit device X exceeds the valid range
0403
Operand KnXm exceeds the valid range
0501
Operand bit device Y exceeds the valid range
0503
Operand KnYm exceeds the valid range
0601
Operand bit device T exceeds the valid range
0604
Operand word device T register exceeds limit
0801
Operand bit device M exceeds the valid range
0803
Operand KnMm exceeds the valid range
0B01
Operand K, H available range error
0D01
DECO operand misuse
0D02
ENCO operand misuse
0D03
DHSCS operand misuse
0D04
DHSCR operand misuse
0D05
PLSY operand misuse
0D06
PWM operand misuse
0D07
FROM/TO operand misuse
0D08 PID
operand
misuse
0D09
SPD operand misuse
0D0A
DHSZ operand misuse
0D0B IST
operand
misuse
0E01
Operand bit device C exceeds the valid range
0E04
Operand word device C register exceeds limit
Check D1137 (Error
step number)
Re-enter the
instruction correctly