beautypg.com

2 error code table (hex), Error code table (hex) -4 – Delta DVP-ES2 User Manual

Page 654

background image

D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

6-4

6.2 Error code Table (Hex)

After you write the program into the PLC, the illegal use of operands (devices) or incorrect syntax in

the program will result in flashing of ERROR indicator and M1004 = ON. In this case, you can find

out the cause of the error by checking the error code (hex) in special register D1004. The address

where the error occurs is stored in the data register D1137. If the error is a general loop error, the

address stored in D1137 will be invalid.

Error code

Description

Action

0001

Operand bit device S exceeds the valid range

0002

Label P exceeds the valid range or duplicated

0003

Operand KnSm exceeds the valid range

0102

Interrupt pointer I exceeds the valid range or duplicated

0202

Instruction MC exceeds the valid range

0302

Instruction MCR exceeds the valid range

0401

Operand bit device X exceeds the valid range

0403

Operand KnXm exceeds the valid range

0501

Operand bit device Y exceeds the valid range

0503

Operand KnYm exceeds the valid range

0601

Operand bit device T exceeds the valid range

0604

Operand word device T register exceeds limit

0801

Operand bit device M exceeds the valid range

0803

Operand KnMm exceeds the valid range

0B01

Operand K, H available range error

0D01

DECO operand misuse

0D02

ENCO operand misuse

0D03

DHSCS operand misuse

0D04

DHSCR operand misuse

0D05

PLSY operand misuse

0D06

PWM operand misuse

0D07

FROM/TO operand misuse

0D08 PID

operand

misuse

0D09

SPD operand misuse

0D0A

DHSZ operand misuse

0D0B IST

operand

misuse

0E01

Operand bit device C exceeds the valid range

0E04

Operand word device C register exceeds limit

Check D1137 (Error

step number)


Re-enter the
instruction correctly


















This manual is related to the following products: