3 . I n s t r u c t i o n S e t

3 - 2 6 9

Program Example 1:

Communication between PLC and VFD-B series AC motor drives (ASCII Mode, M1143 = OFF)

MOV

D1120

H87

M1002

SET

M1120

M1127

Receiving
completed

Set communication protocol as 9600, 8, E, 1

Retain communication protocol

Set receiving time-out as 100ms

Processing received data

Reset M1127

Sending request

X1

X0

MODRD

K1

H2101

K6

Set communication instruction:
D
Data address: H2101
D

ata length: 6 words

evice address: 01

PLC converts the received ASCII data in
D1070~D1085 into Hex data and stores them
into D1050~D1055

MOV

D1129

K100

SET

M1122

RST

M1127

PLC

→ VFD-B , PLC transmits: “01 03 2101 0006 D4”

VFD-B

→ PLC , PLC receives: “01 03 0C 0100 1766 0000 0000 0136 0000 3B”

Registers for data to be sent (sending messages)

Register

Data

Descriptions

D1089 low byte

‘0’

30 H

ADR 1

D1089 high byte

‘1’

31 H

ADR 0

Address of AC motor drive:
ADR (1,0)

D1090 low byte

‘0’

30 H

CMD 1

D1090 high byte

‘3’

33 H

CMD 0

Command code: CMD (1,0)

D1091 low byte

2’

32 H

D1091 high byte

‘1’

31 H

D1092 low byte

‘0’

30 H

D1092 high byte

‘1’

31 H

Starting data address

D1093 low byte

‘0’

30 H

D1093 high byte

‘0’

30 H

D1094 low byte

‘0’

30 H

D1094 high byte

‘6’

36 H

Number of data (count by word)

D1095 low byte

‘D’

44 H

LRC CHK 1

D1095 high byte

‘4’

34 H

LRC CHK 0

Checksum: LRC CHK (0,1)