Delta DVP-ES2 User Manual
Page 632
D V P - E S 2 E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g
6.
Restrictions on diverging sequence: Please refer to section 5.5 for examples
a)
Max. 8 step points could be used for single divergence sequence.
b)
Max. 16 step points could be used for the convergence of multiple diverted sequences.
c)
Users can assign a step in the sequence to jump to any step in another sequence.
7.
Reset step points and disable outputs
a)
Use the ZRST instruction to reset (turn off) a specified step sequence..
b)
Set ON the flag M1034 to disable Y outputs.
8. Latched
step:
The ON/OFF status of the latched step will be memorized when the power of the PLC is
switched off. When the PLC is powered up again, PLC will resume the status before power-off
and executes from the interrupted point. Please be aware of the area for the latched steps.
9.
Special auxiliary relays and special registers: For more details please refer to 5.6 IST
Instruction.
Device
Description
M1040 Disabling
step
transition.
M1041
Step transition start. Flag for IST instruction.
M1042
Enabling pulse operation. Flag for IST instruction.
M1043
Zero return completed. Flag for IST instruction.
M1044
Zero point condition. Flag for IST instruction.
M1045
Disabling “all output reset” function. Flag for IST instruction.
M1046
Indicating STL status. M1046 = ON when any step is ON
M1047
Enabling STL monitoring
D1040
No. of the 1st step point which is ON.
D1041
No. of the 2nd step point which is ON
D1042
No. of the 3rd step point which is ON.
D1043
No. of the 4th step point which is ON
D1044
No. of the 5th step point which is ON.
D1045
No. of the 6th step point which is ON
D1046
No. of the 7th step point which is ON.
D1047
No. of the 8th step point which is ON
5-10